If the test was successful, the drive will stop and return to the configured control
path. The “Motor RS” parameter will contain a new value that is the calculated re-
sistance of the motor.
10.
If the test was not successful, the drive will fault with a “RS Meas. Fail” message
(Fault 34). If the test fails, you may want to try the test again with a different “Rated
Mtr FLA” or different Current Limit percentage.
11.
If the measurement process fails for any reason, it is possible to physically measure
motor resistance by using an ohmmeter and dividing the result by 2. Then enter this
value manually into parameter 514 (Motor RS).
5.6.2 Activating Automatic RS Measurement via Serial Link (Modbus)
1.
Make sure there is no load applied to the motor and that the motor shaft is free to
spin without damage or injury.
2.
Configure the following parameters to the data provided on the nameplate of the
motor:
•
Rated Mtr Volt (509)
•
Rated Mtr FLA (510)
•
Rated Mtr RPM (511)
•
Power Factor (515)
3.
Change parameter “Find Mtr Data” (519) to a value of “Motor RS.” At this point, the
RS Measurement will be armed.
4.
Start the RS Measurement by writing a value of 0x0007 to parameter “SIO Cntl
Word” (904).
5.
The measurement begins as the drive injects voltage to the motor at zero frequency.
The test lasts about two seconds.
6.
If the test was successful, the drive will stop and return to the configured control
path. The “Motor RS” parameter will contain a new value that is the calculated re-
sistance of the motor.
7.
If the test was not successful, the drive will fault with a “RS Meas. Fail” message
(Fault 34). If the test fails, you may want to try the test again with a different “Rated
Mtr FLA” or different Current Limit percentage.
8.
If the measurement process fails for any reason, it is possible to physically measure
motor resistance by using an ohmmeter and dividing the result by 2. Then enter this
value manually into parameter 514 (Motor RS).
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......