vacon • 125
Parameters
6
6.2.5
Preset Freqs
You can use the preset frequency parameters to define certain frequency references in ad-
vance. These references are then applied by activating/inactivating digital inputs connected to
parameters P3.3.3.10, P3.3.3.11 and P3.3.3.12 (
Preset Freq Sel0, Preset Freq Sel1
and
). Two different logics can be selected:
TO
P
RESET
F
REQ
0
TO
7
Value ‘0’ selected for parameter P3.3.3.1:
Preset frequency 0 can be chosen as reference by selecting value 1 for parameter P3.3.1.5.
Other preset frequencies 1 to 7 are selected as reference by dedicating digital inputs for pa-
rameters P3.3.3.10, P3.3.3.11 and/or P3.3.3.12. Combinations of active digital inputs determine
the used preset frequency according to Table 121 below.
The values of the preset frequencies are automatically limited between the minimum and max-
imum frequencies (P3.3.1.1 and P3.3.1.2). See table below.
Preset frequencies 1 to 7:
Table 119.
Selection
number
Selection name
Note
0
Binary coded
Combine activated inputs according to Table 121 to choose the
Preset frequency needed.
1
Number (of inputs
used)
According to how many of the inputs assigned for
Preset fre-
quency selections
are active you can apply the
Preset fre-
quencies
1 to 3.
Table 120.
Required action
Activated frequency
Choose value 1 for parameter
P3.3.1.5
Table 121. Selection of preset frequencies;
= input activated
Activate digital input for
parameter
Activated frequency
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......