Parameters
vacon • 76
Service support: find your nearest Vacon service center at www.vacon.com
6
6.1.4.2
Group 3.3.3: Preset Freqs
Table 52. Preset frequencies parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.3.3.1
0
1
0
182
0 = Binary coded
1 = Number of inputs. Preset
frequency is selected according
to how many of preset speed
digital inputs are active
P3.3.3.2
Hz
5.00
180
Basic preset frequency 0 when
selected by Control reference
parameter (P3.3.1.5).
P3.3.3.3
Hz
10.00
105
Select with digital input:
Preset frequency selection 0
(P3.3.3.10)
P3.3.3.4
Hz
15.00
106
Select with digital input:
Preset frequency selection 1
(P3.3.3.11)
P3.3.3.5
Hz
20.00
126
Select with digital inputs: Preset
frequency selection 0 & 1
P3.3.3.6
Hz
25.00
127
Select with digital input:
Preset frequency selection 2
(P3.3.3.12)
P3.3.3.7
Hz
30.00
128
Select with digital inputs: Preset
frequency selection 0 & 2
P3.3.3.8
Hz
40.00
129
Select with digital inputs: Preset
frequency selection 1 & 2
P3.3.3.9
Hz
50.00
130
Select with digital inputs: Preset
frequency selection 0 & 1 & 2
P3.3.3.10
DigIN
SlotA.4
419
Binary selector for Preset
speeds (0-7). See parameters
P3.3.3.2 to P3.3.3.9.
P3.3.3.11
DigIN
SlotA.5
420
Binary selector for Preset
speeds (0-7). See parameters
P3.3.3.2 to P3.3.3.9.
P3.3.3.12
DigIN
Slot0.1
421
Binary selector for Preset
speeds (0-7). See parameters
P3.3.3.2 to P3.3.3.9.
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......