Quick setup
vacon • 42
24-hour s358 (0)40 837 1150 • Email: [email protected]
8
8.
Q
UICK
SETUP
Following these instructions, you can easily and fast set up your Modbus for use:
1
Choose control place.
A. Press LOC/REM button on keypad to select
Remote Control Place
B. Select
Fieldbus
as remote control place:
Main Menu
>
Quick Setup (M1)
>
Rem. Ctrl. Place (P1.15) > FieldbusCTRL
2
Make these settings in the master software
A. Set
Control Word
to
‘0’
(2001)
B. Set
Control Word
to
‘1’
(2001)
C. Frequency converter status is RUN
D. Set Reference value to
‘5000’
(50.00%) (2003).
E.
Actual speed
is 5000 (25.00 Hz if MinFreq is 0.00 Hz and MaxFreq is 50.00 Hz)
F. Set
Control Word
to ‘
0’
(2001)
G. Frequency converter status is STOP.