8
vacon • 68 Assembly instances implemented by vacon® 100 family
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8.2.1.3
Assembly Instance 128
The contents of the assembly are otherwise identical to the output assembly 111, except that the
second octet of the assembly is the high octet of FBGeneralControlWord instead of
FBFixedControlWord.
Table 71.
Instance
Octet
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
128
(length 20)
0
FBFixedControlWord (Low Octet)
1
FBGeneralControlWord (High Octet)
2
FBSpeedReference (Low Octet) in %
3
FBSpeedReference (High Octet) in %
4
FBProcessDataIn1 (Low Octet)
5
FBProcessDataIn1 (High Octet)
6
FBProcessDataIn2 (Low Octet)
7
FBProcessDataIn2 (High Octet)
8
FBProcessDataIn3 (Low Octet)
9
FBProcessDataIn3 (High Octet)
10
FBProcessDataIn4 (Low Octet)
11
FBProcessDataIn4 (High Octet)
12
FBProcessDataIn5 (Low Octet)
13
FBProcessDataIn5 (High Octet)
14
FBProcessDataIn6 (Low Octet)
15
FBProcessDataIn6 (High Octet)
16
FBProcessDataIn7 (Low Octet)
17
FBProcessDataIn7 (High Octet)
18
FBProcessDataIn8 (Low Octet)
19
FBProcessDataIn8 (High Octet)