EtherNet/IP
vacon • 22
24-hour s358 (0)201 212 575 • Email: [email protected]
6
6.4.4
Supported CIP and Vendor Objects
The Communication Interface supports the following object classes.
789
d
/ 315
h
Invalid segment in connection path
Range 320h – 7FFh are vendor specific
800
d
/ 320
h
Internal: Connection disabled
64258
d
/ FB02
h
Internal: Bad socket
64259
d
/ FB03
h
Internal: Bad originator to target net parameter
64260
d
/ FB04
h
Internal: Bad target to originator net parameter
64261
d
/ FB05
h
Internal: Bad UDP port
64262
d
/ FB06
h
Internal: Join multicast
64263
d
/ FB07
h
Internal: Prepare IO packet
64267
d
/ FB0B
h
Internal: Consumption
64268
d
/ FB0C
h
Internal: FW close
64270
d
/ FB0E
h
Internal: Adapter stopped
Table 10. CIP Objects
Type
Class
Object
Details
Required by Ether-
Net/IP
1
Identity Object
See chapter 7.1.1
2
Message Router Object
See chapter 7.1.2
4
Assembly Object
See chapter 7.2.1
6
Connection Manager Object
See chapter 7.1.3
245
d
/ F5
h
TCP/IP Interface Object
See chapter 7.1.4
246
d
/ F6
h
Ethernet Link Object
See chapter 7.1.5
Required by Drive
Profile
40
d
/ 28
h
Motor Data Object
See chapter 7.2.2
41
d
/ 29
h
Control Supervisor Object
See chapter 7.2.3
42
d
/ 2A
h
AC/DC Drive Object
See chapter 7.2.4
Vendor-Specific
160
d
/ A0
h
Vendor Parameters Object
See chapter 7.3.1
161
d
/ A1
h
Motor Control Mode Object
See chapter 7.3.3
162
d
/ A2
h
Fault History Object
See chapter 7.3.4
190
d
/ BE
h
Assembly Instance Selector
Object
See chapter 7.3.2
Table 9. Connection Manager Object Error codes
Extended Status
Descriptions
Содержание 100 flow