Common Industrial Objects implemented by vacon® 100 family
vacon • 31
24-hour s358 (0)201 212 575 • Email: [email protected]
7
7.1.4.1
Instance Attributes
Instance Attribute “Status”
This attribute presents the status of the TCP/IP network interface.
Instance
Attributes
Id
Access rule
Name
Datatype
Description
1
Get
Status
DWORD
Interface status
2
Get
Configuration
Capability
DWORD
Interface capability flags
3
Get/set
Configuration
Control
DWORD
Interface control flags
4
Get
Physical Link
Object
STRUCT of
Path to physical link object
Path size
UINT
Size of the path
Path
Padded
EPATH
Logical segments identify-
ing the physical link object
5
Get/set
Instance Config-
uration
STRUCT of
TCP/IP network interface
configuration
IP Address
UDINT
The device’s IP address
Network Mask
UDINT
The device’s network mask
Gateway
Address
UDINT
Default gateway address
Name Server
UDINT
Primary name server
Name Server 2
UDINT
Secondary name server
Domain Name
STRING
Default domain name
6
Get/set
Host Name
STRING
Host name
10
d
/
0A
h
Get/set
Select ACD
BOOL
Activates the use of ACD
(enabled by default)
11
d
/
0B
h
Get
Last Conflict
Detected
STRUCT
of:
Structure containing infor-
mation related to the last
conflict detected.
ACD activity
USINT
State of ACD activity
Remote MAC
Array of 6
USINT
MAC address of last conflict
source.
ARP PDU
Array of 28
USINT
Copy of the last ARP PDU in
which a conflict was
detected.
Instance
Services
Id
Name
Description
1
Get_Attributes_All
Returns content of all (implemented)
attributes in the instance
14
d
0E
h
Get_Attribute_Single
Used to read single attribute value.
16
d
10
h
Set_Attribute_Single
Used to write a single attribute value.
Table 15. TCP/IP interface object