76
•
VACON
T
ECHNICAL
DATA
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
11
11.2 Power ratings
11.2.1 Vacon 10 - Mains voltage 115 V
11.2.2 Vacon 10 – Mains voltage 208-240 V
* The maximum ambient operating temperature of these drives is +40 °C.
Mains voltage
115
V, 50/60 Hz,
1
~ series
Freq.
converter
type
Rated loadability
Motor
shaft
power
Nominal
input
current
Mechanical
size
Weight
(kg)
100% contin.
current I
N
[A]
150% over-
load current
[A]
P
[KW]
[A]
0001
1.7
2.6
0.25
9.2
MI2
0.70
0002
2.4
3.6
0.37
11.6
MI2
0.70
0003
2.8
4.2
0.55
12.4
MI2
0.70
0004
3.7
5.6
0.75
15
MI2
0.70
0005
4.8
7.2
1.1
16.5
MI3 0.99
Table 11.2: Vacon 10 rated loadability, 115 V
Mains voltage 208 - 240 V, 50/60 Hz,
1
~ series
Freq.
converter
type
Rated loadability
Motor
shaft
power
Nominal
input
current
Mechanical
size
Weight
(kg)
100% contin.
current I
N
[A]
150% over-
load current
[A]
P
[KW]
[A]
0001
1.7
2.6
0.25
4.2
MI1
0.55
0002
2.4
3.6
0.37
5.7
MI1
0.55
0003
2.8
4.2
0.55
6.6
MI1
0.55
0004
3.7
5.6
0.75
8.3
MI2
0.7
0005
4.8
7.2
1.1
11.2
MI2 0.7
0007
7.0
10.5
1.5
14.1
MI2
0.7
009*
9.6
14.4
2.2
22.1
MI3
0.99
Table 11.3: Vacon 10 power ratings, 208-240 V,
1
~
Содержание 10 PFC
Страница 1: ...vacon 10 ac drives vacon 10 pfc user manual...
Страница 2: ......
Страница 15: ...INSTALLATION VACON 13 24 hour support 0 201 212 575 Email vacon vacon com 3 MI1 MI3 3P 230 V POWER LOSS...
Страница 16: ...14 VACON INSTALLATION Tel 358 0 201 2121 Fax 358 0 201 212 205 3...
Страница 17: ...INSTALLATION VACON 15 24 hour support 0 201 212 575 Email vacon vacon com 3 MI1 MI3 1P 230 V POWER LOSS...
Страница 18: ...16 VACON INSTALLATION Tel 358 0 201 2121 Fax 358 0 201 212 205 3...
Страница 25: ...INSTALLATION VACON 23 24 hour support 0 201 212 575 Email vacon vacon com 3 Figure 3 14 MI3 screws...
Страница 81: ......