P
ARAMETER
DESCRIPTIONS
VACON
•
71
24-hour support (0)201 212 575 • Email: [email protected]
10
If the motor t6-time (t6 is the time in seconds the motor can safely operate at
six times the rated current) is known (given by the motor manufacturer), it can
be used as a basis for setting the time constant parameter. As a rule of thumb,
the motor thermal time constant in minutes is equal to 2xt6. If the drive is in
stop mode, the time constant is internally increased to three times the set pa-
rameter value. See also Figure 10.7.
Figure 10.7: Motor temperature calculation