GROUP 2. Advanced PFC settings
2.1
W
ORK
PRESSURE
2
By enabling digital input DI2, you can work with the pressure inserted in this
parameter.
2.2
A
CCELERATION
Acceleration time from OHz to maximum frequency.
2.3
D
ECELERATION
Deceleration time from maximum frequency to OHz.
2.4
PI
CONTROLLER
GAIN
This parameter defines the gain of the PI controller. If this parameter is set to
100%, a 10% change in the error value results in a 10% change in controller
output.
2.5
PI
CONTROLLER
I -
TIME
This parameter defines the integration time of the PI controller. If this param-
eter is set to 1.00 second, controller output changes by a value corresponding
to the output caused by the gain every second. (Gain/Error)/s.
2.6
PID
ERROR
VALUE
INVERSION
This parameter enables users to invert the PID controller error value (and
therefore PID controller operations).
0 = Not inverted
1 = Inverted
2.7
A
UTOCHANGE
I
NTERVAL
After the time set by this parameter has elapsed, autochange takes place if
the load used is less than the level set in parameters P2.9 (autochange inter-
val limit) and 2.8 (Maximum number of auxiliary pumps). If the load exceeds
the value in parameter 2.9, autochange will not occur until the load is below
this limit.
• Timing is enabled only if Start/Stop request is activated.
• Timing is reset after autochange takes place or when the Start request is re-
moved.
2.9
A
UTOCHANGE
:
INTERVAL
LIMIT
These parameters set the maximum load for autochange to take place. This
level is defined as follows:
• Autochange can take place if the number of auxiliary pumps running is lower
than the value in parameter 2.89, autochange may take place.
Содержание 10 PFC
Страница 1: ...vacon 10 ac drives vacon 10 pfc user manual...
Страница 2: ......
Страница 15: ...INSTALLATION VACON 13 24 hour support 0 201 212 575 Email vacon vacon com 3 MI1 MI3 3P 230 V POWER LOSS...
Страница 16: ...14 VACON INSTALLATION Tel 358 0 201 2121 Fax 358 0 201 212 205 3...
Страница 17: ...INSTALLATION VACON 15 24 hour support 0 201 212 575 Email vacon vacon com 3 MI1 MI3 1P 230 V POWER LOSS...
Страница 18: ...16 VACON INSTALLATION Tel 358 0 201 2121 Fax 358 0 201 212 205 3...
Страница 25: ...INSTALLATION VACON 23 24 hour support 0 201 212 575 Email vacon vacon com 3 Figure 3 14 MI3 screws...
Страница 81: ......