1. Scroll the parameters with the button
, the display order is: MAX1-MIN1-MAX2-
MIN2-CLR-SEt1-H01-L01-SEt2-H02-L02-n-y-r-S-F-Pt-tH1-P1-PS1-b1-b2
2. Increase or decrease the value with the button
or
;
3. Press
to temporarily store the modified value and return to the display parame-
ters.
4. Repeat steps 1 to 3 if other parameters need to be modified.
5. Press and hold
for more than 3 seconds to store the modified parameter and
return to the displayed parameter category.
S/N
Menu
Parameter
Range
Recommend-
ed Set Value
Remarks
1
MAX1
---
Maximum value of upper temperature in the
current time period
2
MIN1
---
Minimum value of upper temperature in the
current time period
3
MAX2
---
Maximum value of lower temperature in the
current time period
4
MIN2
---
Minimum value of lower temperature in the cur-
rent time period
5
CLR
0~1
1
0: Clear the minimum and maximum tempera-
ture value in the current time period
1: Do not clear the minimum and maximum
temperature value in the current time period
6
SEt1
0
~
10
℃
5
Set temperature of the refrigerator chamber
7
H01
0.0
~
10.0
3
Upper deviation of high temperature alarm in
refrigerator chamber
8
L01
0.0
~
10.0
3
Lower deviation of high temperature alarm in
refrigerator chamber
9
SEt2
-10
~
-25
-25
Set temperature of the freezer chamber
10
H02
0.0
~
10.0
5
Upper deviation of high temperature alarm in
freezer chamber
11
L02
0.0
~
10.0
5
Lower deviation of high temperature alarm in
freezer chamber
12
n
---
--
View current date - year
13
y
---
--
View current date - month
14
r
---
--
View current date - day
15
S
---
--
View current date - hour
16
F
---
--
View current date - minute
17
Pt
0-240 minutes
20
Print interval
18
tH1
20.0~50.0
32
High ambient temperature alarm value
19
P1
1~5
5
Selection of door heating modes
20
PS1
0~9999
0005
User menu password setting
21
b1
---
--
Hardware version
22
b2
---
--
Software version
15