92077r14
www.vac.se
V200 POSITIONER
6
2.3.3 4-20mA transmitter setup
1.
Determine the direction for
increasing mA output. Direct (CCW)
or Reverse (CW).
2.
The direction of rotation is simply
determined by watching the positioner
drive shaft(1).
3.
CCW rotation: the potentiometer lead
connector(2) fitted with the Black or Blue
colored lead facing to the left.
4.
CW rotation: the potentiometer lead
connector(2) fitted with the Black or Blue
colored lead facing to the right.
The position transmitter can be calibrated in a
range from 25° up to 115°.
25° - 70° with Jumper(3).
70° - 115° no Jumper(3).
The Position Transmitter is
shipped for direct (CCW)
turning, range 0-90°
2.3.4 Connecting the control signal
1. Connect the signal cable to the proper
pole on the terminal block(1).
Maximum cable size AWG 13 (2.5 mm
2
)
1
1
2
2
3