4.

Hold the prepared positioner (with the mount bracket 

1

 still

loose) on the actuator so that the follower pin for the lever
enters the follower guide to determine which tap holes on 
the positioner must be used for the mount bracket. 

5.

Secure the mount bracket 

1

 with screws 

2

 and washers 

3

using the relevant tap holes on the positioner housing.

Tighten the screws as evenly as possible to ensure 
subsequent linearity. Align the mount bracket in the oblong 
hole to ensure that the operating range is symmetrical (lever 
moves between the arrow marks 

4

). 

M10418-01

1

2

3

4

Figure 9:  Mounting on a cast iron yoke 

1.

Attach the mount bracket 

2

 with screw 

4

 and washer 

3

 

to the cast iron yoke 

1

or 

M10419-01

1

2

3

4

5

Figure 10:  Mounting on a columnar yoke 

1.

Hold the mount bracket 

3

 in the proper position on the

columnar yoke 

2

2.

Insert the U-bolts 

1

 from the inside of the columnar yoke 

2

through the holes of the mount bracket.

3.

Add the washers 

4

 and nuts 

5

Tighten the nuts so that they are hand-tight.

Note 

Adjust the height of the positioner on the cast iron yoke or 
columnar yoke until the lever is horizontal (based on a visual 
check) at half stroke of the valve. 

Содержание D500

Страница 1: ...ce performance ratio Fully automatic determination of the control parameters and adaptation to the positioner allow for considerable time savings as well as optimum control behavior Due to its charact...

Страница 2: ...dentification 14 Name plate 14 6 Transport and storage 15 Inspection 15 Transporting the device 15 Storing the device 15 Ambient conditions 15 Returning devices 15 7 Installation 15 Safety instruction...

Страница 3: ...2 Menu Display 58 Menu Controller 59 Menu Input Output 62 Menu Communication 68 Menu Diagnosis 69 Menu Device Info 71 Menu Service 72 10 Diagnosis error messages 74 Calling up the error description 74...

Страница 4: ...d if expressly permitted by these instructions Information and symbols on the product must be observed These may not be removed and must be fully legible at all times The operating company must strict...

Страница 5: ...or any other network as the case may be Operator shall establish and maintain any appropriate measures such as but not limited to the installation of firewalls application of authentication measures e...

Страница 6: ...ded instructions on different types of protection and installation techniques concerned rules and regulations as well as general principles of zoning The person must possess the appropriate competence...

Страница 7: ...ned Only use cable glands which are approved for the type of protection and correspond to IP rating IP 6X Danger due to propagating brush discharge must be avoided Operation in temperature class T6 Du...

Страница 8: ...e emergency shutdown function Terminals 85 86 Temperature class T1 T6 Ui 30 V Pi 1 W Ci 5 3 nF Li negligibly small Module for analog feedback AO Terminals 31 32 Temperature class T1 T4 Temperature cla...

Страница 9: ...nals 85 86 Electrical values UN 30 V Module for analog feedback AO Terminals 31 32 Electrical values IN 22 mA UN 30 V Module for universal input UAI Terminals 21 22 Electrical values IN 22 mA Umax 30...

Страница 10: ...III Div 2 T4 or T6 Class I Zone 2 AEx nA IIC T4 or T6 T4 Ta 40 to 85 C 40 to 185 F T6 Ta 40 to 40 C 40 to 104 F IP64 Mounting The installation commissioning maintenance and repair of devices in areas...

Страница 11: ...pagating brush discharge must be avoided Operation in temperature class T6 During operation in temperature class T6 when the equipment is partially or fully depressurized ensure that there is no possi...

Страница 12: ...nction Terminals 85 86 Temperature class T1 T6 Ui 30 V Pi 1 W Ci 5 3 nF Li negligibly small Module for analog feedback AO Terminals 31 32 Temperature class T1 T4 Temperature class T6 Ui 30 V Ui 28 V I...

Страница 13: ...0 mA Bus connection 2 Digital input 3 Alarm output 4 Supply air 5 Output 1 6 Output 2 7 Analog feedback 8 Digital feedback 9 Emergency shutdown module j Universal input k Pressure sensor l Limit alarm...

Страница 14: ...edback output Universal analog input Safety shut down Pressure sensors Electr limit switch Mech limit switch low Mech limit switch high Contactless pos Sensor H Slot1 Slot2 X X X 1 9 j k 3 4 5 6 7 l m...

Страница 15: ...der confirmation of the supplier apply Ambient conditions Transport and storage Ambient temperature range 40 85 C 40 185 F Relative humidity 75 annual average Returning devices For the return of devic...

Страница 16: ...l connection is carried out as described in chapter EDP300 Remote Sensor Electrical Connection on page 25 Note To connect the EDP300 Remote Sensor a cable with the following specifications needs to be...

Страница 17: ...for linear actuators is 45 symmetrically to the longitudinal axis The usable span within the operating range is at least 25 recommended figure 40 The usable span does not necessarily need to run symme...

Страница 18: ...l Clamp plates m Follower guide Figure 6 Components of attachment kit M10411 01 1 2 3 4 Figure 7 Attaching a follower guide to the actuator 1 Tighten the screws so that they are hand tight 2 Attach th...

Страница 19: ...e operating range is symmetrical lever moves between the arrow marks 4 M10418 01 1 2 3 4 Figure 9 Mounting on a cast iron yoke 1 Attach the mount bracket 2 with screw 4 and washer 3 to the cast iron y...

Страница 20: ...range for linear actuators 30 to 30 minimum range 25 Note After mounting check whether the positioner is operating within the sensor range Position of actuator bolt The actuator bolt for moving the p...

Страница 21: ...ry actuator For mounting on part turn actuators in accordance with VDI VDE 3845 the following attachment kit is available M10130 01 1 2 3 4 5 6 7 8 9 Figure 16 Components of attachment kit Adapter 1 w...

Страница 22: ...of the actuator must be considered when determining the adapter position on axis 1 For this purpose the feedback shaft can be adjusted manually so that the adapter 3 can be attached in the correct pos...

Страница 23: ...off the power supply The electrical connection may only be established by authorized specialist personnel Notices on electrical connection in this instruction must be observed otherwise electric safe...

Страница 24: ...mns Connections for inputs and outputs Terminal Function comments 11 12 Analog input AI or field bus connection 81 82 Digital input DI 83 84 Digital output DO2 51 52 Limit alarm SW1 Option module 41 4...

Страница 25: ...puts Terminal Function comments 1 2 3 EDP300 Control Unit 51 52 Limit switch Limit 1 with proximity switch optional 41 42 Limit switch Limit 2 with proximity switch optional 51 52 53 Limit switch Limi...

Страница 26: ...als 31 32 Signal range 4 to 20 mA split ranges can be parameterized Supply voltage two wire technology 24 V DC 10 to 30 V DC Characteristic curve rising or falling configurable Deviation 1 Module for...

Страница 27: ...o slots for the option modules Any combination of different option modules is possible However identical option modules cannot be combined Limit switch The limit switch can either be equipped with pro...

Страница 28: ...ately 6 mm 0 24 in 2 Connect the wires to the connecting terminals in line with the connection diagram Wire cross sectional areas Basic device Electrical connections 4 to 20 mA input Screw terminals m...

Страница 29: ...res 0 14 to 0 75 mm2 AWG26 to AWG20 Flexible with wire end sleeve no plastic sleeve 0 25 to 0 5 mm2 AWG23 to AWG22 Flexible with wire end sleeve with plastic sleeve 0 5 to 1 mm2 AWG21 to AWG18 Limit s...

Страница 30: ...ack Digital position feedback Emergency shutdown module Universal input Housing 2 EDP300 Remote Sensor contains the position sensor and is suitable for mounting on linear or rotary actuators If necess...

Страница 31: ...ten the screws of the terminals so that they are hand tight Use wire end ferrules when connecting The electrical connections of the EDP300 Control Unit and the optional modules are carried out as desc...

Страница 32: ...ctronics and pneumatics along with the following options where applicable Analog position feedback Digital position feedback Emergency shutdown module Universal input Any position sensor 4 to 80 k may...

Страница 33: ...the option module so that the plug points to the right 3 Using a small amount of pressure guide the option module into the slot from the side and press it down firmly 4 Secure the option module in the...

Страница 34: ...ption modules and remove them from the side 4 If present remove the mechanical position indication and screw off the shaft extension as well as the mechanical alarm signaling unit if applicable 5 Remo...

Страница 35: ...the metal tag of proximity switch 2 upper contact on the axis until contact is made i e just before it is inserted in the proximity switch The slot sensor enters proximity switch 2 when the feedback...

Страница 36: ...e possibility of this occurring it is recommended to install a pressure compensation valve between the springless chamber and the supply air for these types of applications It enables the increased pr...

Страница 37: ...100 55 to 100 8 Commissioning Safety instructions Note The electrical power supply and supply air pressure data indicated on the name plate must be complied with during commissioning Before switching...

Страница 38: ...nt end positions 45 0 Pos Ang Check the end positions The angle of rotation is displayed in degrees Recommended range between 30 to 30 for linear actuator between 45 to 45 for rotary actuator Moving t...

Страница 39: ...cover open Menu navigation M10145 01 1 2 5 Menu 3 4 5 Exit Select 1 Operating buttons for menu navigation 2 Indication of menu designation 3 Indication of menu number 4 Marking to indicate relative p...

Страница 40: ...el Operating modes menu In the operating modes menu the Auto Adjust function can be started for commissioning purposes You can also change the operating modes and switch to the configuration level Con...

Страница 41: ...l input activated Diagnostic message pending Error pending Maintenance message pending Switching to the information level Operator Menu On the information level the operator menu can be used to displa...

Страница 42: ...ing mode results more from the system structure than from the changing behavior of the system meaning that if a stable adaptive operating mode can be obtained over several days of control variations i...

Страница 43: ...gh speed mode CAUTION Danger of crushing If air escapes due to a leakage the position will not be readjusted Configured stroke limit positions and stroke times are not effective in manual mode When th...

Страница 44: ...e configuration level parameterization The device parameters can be displayed and changed on the configuration level Operating mode Auto Adjust O Adaptive O Control O Manual SP O Manual Sensor Configu...

Страница 45: ...ut the area in which the error has occurred Process display Electronic The error messages are divided into four groups in accordance with the NAMUR classification scheme The group assignment can only...

Страница 46: ...be visible in it Easy Setup 1 Language Actuator Type Bolt Position Vent Position Tight Shut 0 Control at 0 Tight Shut 100 Control at 100 Autoadjust Mode Start Autoadjust Device Setup 2 Actuator Type...

Страница 47: ...back Analog Out Min Analog Out Max Feedbk Charact AO Alarm Mask Alarm Maintenan Alarm OoSpec Alarm Check Fct Alarm Failure AO Simulation Digital Feedback Switch 1 Switch 1 Funct Switch 1 Value Switch...

Страница 48: ...input UI SP Value Max UI SP Value Min UI Damping UI Charact UI Out Value Min UI Out Value Max Communication 6 HART Version Find Device Diagnosis 7 Partial Stroke PS Configuration PS Interval PS Start...

Страница 49: ...g Date Commun Tag Device Address Descriptor Device Message Pneumatic Type Stroke Time Up Stroke Time Dn Service 9 Service Mode Factory Setting Adjust Sensors Adjust All Adjust Outputs Pneumatic Remote...

Страница 50: ...ompletely vented Tight Shut 0 0 0 to 45 0 The shut off value is a percentage of the working range from which the 0 position is approached Once the specified position limit value is reached the actuato...

Страница 51: ...tomatic adjustment blocked Note On valves where slip stick effect is significant valve vibration can be reduced by increasing the value of the Zone parameter Start Autoadjust Start The following value...

Страница 52: ...r Bolt On Stem actuator bolt on the valve stem Factory setting Bolt On Lever Vent Position Position 0 Position 100 Use this parameter to specify which position is to be shown in the display when outpu...

Страница 53: ...ter to set a damping value for the setpoint signal SP Ramp Up Off up to 0 to 200 seconds Here the stroke time for the actuator can be increased A setpoint change is not directly transferred to the pos...

Страница 54: ...loop In addition to five predefined characteristic curves you can also select a user configurable characteristic curve which can only be generated and saved in the device via a PC with the appropriate...

Страница 55: ...manually rotated old min new max old max new min the device no longer reacts to set point changes A constant process value of 128 flashes on the display Lower Valve Rng 0 0 to 100 0 Normally the valve...

Страница 56: ...ent of a power supply failure electric or pneumatic and in manual mode the mechanical end positions are approached Do not reach into the adjustment mechanism Lower Working Rng 0 0 to 100 0 The working...

Страница 57: ...s changed the switching points of the binary feedback opposite the valve area which had possibly been previously adjusted will shift Tight Shut 100 55 0 to 100 The shut off value is a percentage of th...

Страница 58: ...only be entered in plain text using a DTM EDD Display Value Position Position Setpoint Setpoint mA Deviation Temperature Univ Inp Press Y1 Press Y2 Diff Press Supply Press Use this parameter to select...

Страница 59: ...ing compensated This can be prevented by reducing the speed of the dead band approach DB Approach DB Control time 0 to 30 s In some cases it can happen that the valve continues moving slowly after rea...

Страница 60: ...alue should be set separately for both positioning directions up down For most actuators satisfactory control behavior is achieved with a KP value between 2 0 and 10 0 Note The control precision is no...

Страница 61: ...r stops outside the dead band Y Offset Down 1 to 100 0 Use this parameter to adjust the Y offset for the down positioning direction towards 0 The offset for the set point signal linearizes the behavio...

Страница 62: ...Feedbk Charact AO Alarm Mask AO Simulation The current valve position or when the backward calculated characteristics of the valve influence is reported back as a current signal via the analog feedbac...

Страница 63: ...matic outputs Partial Stroke Test Start Partial Stroke Test Service Required Issue diagnosis bit via binary feedback Safety Position Approach safety position Conf Locked Block local configuration Pane...

Страница 64: ...mA However the current range must not be smaller than 10 1 6 mA Analog Out Max 5 6 to 20 0 mA Use this parameter to specify the upper current range limit for the analog feedback The current range corr...

Страница 65: ...Switch 2 simulation SW 2 Mask Map Alarm Maintenan Alarm OoSpec Alarm Check Fct Alarm Failure Switch 2 Sim The function of switch 2 MASK MAP is configured in this parameter group SW 2 Mask Map Switch 2...

Страница 66: ...arm Check Fct Alarm Failure Switch 1 Sim Use this parameter to simulate the switch function Off Simulation deactivated Menu SW 2 Mask Map Menu parameter Value range Description Input Output Digital Fe...

Страница 67: ...Universal input UI SP Value Max 4 0 to 20 0 mA Use this parameter to specify the upper current range limit for the universal input UI SP Value Min 4 0 to 20 0 mA Use this parameter to specify the low...

Страница 68: ...ted In the event of a switch from HART 7 to HART 5 if write protection has been activated via HART 7 it is deactivated when the device is restarted When switching from HART 5 to HART 7 device addresse...

Страница 69: ...an individual bar graph The valve ranges are divided up as follows 0 0 10 10 20 20 30 30 40 40 50 50 60 60 70 70 80 80 90 90 100 100 The histograms support valve diagnostics and allow conclusions to b...

Страница 70: ...is automatically determined by Auto Adjust only in Auto Adjust mode Valve Ranges Full Dead Time Use this parameter dead time to set the time in which the valve should have moved out of the end positi...

Страница 71: ...he device information is displayed here The description can only be entered and changed using a PC DTM EDD Pneumatic Type Single Safe Single Freeze Double Safe Double Freeze The type of pneumatics tha...

Страница 72: ...s the device triggers a sequence to vent the outputs The end points of the valve are approached without the brakes being applied Do not reach into the adjustment mechanism Supply Pressure Supply air p...

Страница 73: ...tered values are accepted by using Confirm Sensor Position 0 Position Use this parameter to set the fine adjustment of the 0 position after a sensor replacement The current position of the sensor rang...

Страница 74: ...n Information Back Exit The error message is shown on the display according to priority The first line shows the area in which the error has occurred The second line shows the unique error number It i...

Страница 75: ...unction deactivated X 13 53 Stroke counter limit exceeded Many valve strokes Valve requires maintenance X 14 54 Travel counter limit exceeded Many valve strokes or vibrating valve Valve requires maint...

Страница 76: ...tuator 32 41 Y Offset Up exceeded Excessive dynamic friction Valve requires maintenance X Actuator 33 42 Y Offset Down exceeded Excessive friction Valve requires maintenance X Actuator 34 61 Friction...

Страница 77: ...Special Requirements 48 81 Pressure measurement defect Print option optional module defective Replace Print option optional module X Electronics 202 Extern access Communication with the device is perf...

Страница 78: ...ng hazardous materials the owner of hazardous waste is responsible for its disposal or must observe the following regulations for shipping purposes All devices delivered to ABB must be free from any h...

Страница 79: ...n data and contributing factors Output Y1 Increasing set point signal 0 to 100 Increasing pressure at output Decreasing set point signal 0 to 100 Decreasing pressure at output Action set point signal...

Страница 80: ...he positioner can be fitted with a contactless position sensor Pressure option The pressure option comprises 3 absolute pressure sensors which facilitate pressure based valve diagnostics valve signatu...

Страница 81: ...e Fax Email Device details Type Serial no Reason for the return description of the defect Was this device used in conjunction with substances which pose a threat or risk to health F Yes F No If yes wh...

Страница 82: ...82 17 Appendix Control Drawing 901305...

Страница 83: ...83...

Страница 84: ...84 17 Appendix Control Drawing 901305...

Страница 85: ...85...

Страница 86: ...86 17 Appendix Control Drawing 901305...

Страница 87: ...87...

Страница 88: ...turer ABB Automation Products GmbH Process Automation Schillerstr 72 32425 Minden Germany Tel 49 571 830 0 Fax 49 571 830 1806 Customer service center Tel 49 180 5 222 580 Mail automation service de a...

Страница 89: ...VALVE ACCESSORIES CONTROLS 200 Jade Park Chelsea AL 35043 TEL 205 678 0507 info vacaccessories com...

Отзывы: