75
Possible error messages
No.
Priority Fault message
Possible cause
Troubleshooting the Instrument
F
C
S
M
Group
1
90
Position
measurement
Failure*
Defective position sensor
Replace position sensor
X
Sensor
2
91
Valve blocked
Friction too high
Valve requires maintenance
X
Actuator
3
50
Positioning timeout - Check
valve maintenance
Positioning time up-scaled
friction high
Valve requires maintenance
X
Actuator
4
51
Positioning unstable
Change disturbance variables
Select ‘Adaptive Control’ mode
X
Configuration
5
49
Position out of travel range Mounting kit is bent
Check mounting conditions
X
Process
6
52
Zero-Point displacement
Valve seat is damaged
Valve requires maintenance
X
Process
7
43
kp up exceeded
Friction too high
Valve requires maintenance
X
8
44
kp Down exceeded
Friction too high
Valve requires maintenance
X
9
92
Setpoint failure electronics Faulty electronics
Replace electronics
X
Electronics
10
70
Setpoint out of range
Defective DCS card
Replace DCS card
X
Special
Requirements
11
80
Device not calibrated
Auto adjust has not yet been
executed
Execute auto adjust
X
Configuration
12
79
Controller inactive
Test function activated
Test function deactivated
X
13
53
Stroke counter limit
exceeded
Many valve strokes
Valve requires maintenance
X
14
54
Travel counter limit
exceeded
Many valve strokes or vibrating
valve
Valve requires maintenance
X
15 55 Electronic
temperature
measurement failure
Temperature sensor defective
Replace electronics
X
Electronics
16 71 Electronic
temperature
out
of limits
Temperature is too high or too
low
Check mounting conditions
X
Special
Requirements
17
94
Configuration data failure Output piping mixed up
Check mounting conditions
X
Actuator
18
95
Electronics - NV chip defect Faulty electronics
Replace electronics
X
Electronics
19
96
Non volatile data defect
Faulty electronics
Replace electronics
X
Electronics
20
56
Leakage during operation Leakage in actuator, piping,
connections, or positioner
Start leakage test
X
Actuator
21
57
Leakage chamber 1
Leakage in chamber 1 of the
actuator or pneumatics output
line 1
Check chamber 1 of the actuator or
pneumatics output line 1
X
Actuator
22
58
Leakage chamber 2
Leakage in chamber 2 of the
actuator or pneumatics output
line 2
Check chamber 2 of the actuator or
pneumatics output line 2
X
Actuator
* If the ‘positioning timeout’ alarm has been set, the positioner monitors if the position changes more than 0.1 % over 5 seconds. If not, a ‘Valve Blocked’
diagnosis notice is output. No alarm is output in the end position.
Содержание D500
Страница 82: ...82 17 Appendix Control Drawing 901305...
Страница 83: ...83...
Страница 84: ...84 17 Appendix Control Drawing 901305...
Страница 85: ...85...
Страница 86: ...86 17 Appendix Control Drawing 901305...
Страница 87: ...87...
Страница 89: ...VALVE ACCESSORIES CONTROLS 200 Jade Park Chelsea AL 35043 TEL 205 678 0507 info vacaccessories com...