26
… 7 Installation
… Electrical connections
Set point signal analog (two-wire technology)
Terminals
+11
/
Æ
12
Nominal operating range
4 to 20 mA
Limit values
Maximum: 50 mA (overload)
Minimum: 3.6 mA
Starting at
t
3.8 mA
Load voltage
9.7 V at 20 mA
Impedance
485
έ
at 20 mA
Digital input DI
Terminals
+81 /
Æ
82
Supply voltage
24 V DC (12 to 30 V DC)
Input ‘logical 0’
0 to 5 V DC
Input ‘logical 1’
11 to 30 V DC
Input Current
Maximum 4 mA
Digital output DO
Terminals
+83 /
Æ
84
Supply voltage
5 to 30 V DC
(Control circuit to DIN 19234/NAMUR)
Switching state logical
‘0’: current > 0.35 mA to < 1.2 mA
‘1’: Current > 2,1 mA
Direction of action
standard logical ‘0’ or logical ‘1’
(configurable)
Option modules
Module for analog feedback AO*
Without any signal from the positioner (e.g. ‘no power’ or
‘initializing’) the module sets the output to > 20 mA (alarm level).
Terminals
+31 /
Æ
32
Signal range
4 to 20 mA (split ranges can be parameterized)
Supply voltage, two-wire
technology
24 V DC (10 to 30 V DC)
Characteristic curve
rising or falling (configurable)
Deviation
< 1 %
Module for digital feedback
SW1, SW2*
Two switches for binary position feedback (position adjustable
within the range of 0 to 100 %, ranges cannot overlap)
Terminals
+41 /
Æ
42, +51 /
Æ
52
Supply voltage
5 to 11 V DC
(Control circuit to DIN 19234/NAMUR)
Signal current
< 1,2 mA: Switching state logical ‘0’
> 2,1 mA: Switching state logical ‘1’
Direction of action
standard logical ‘0’ or logical ‘1’ (configurable)
Module for universal input UAI*
Module for a 4 to 20 mA input for universal use.
The range can be scaled. It is used for advanced valve
diagnostics. For example, an ultrasonic sensor can be connected
to detect a faulty valve seat or a phonometer can be connected
to detect cavitation.
The limit values for detecting up-scaling can be freely selected.
Terminals
+21 /
Æ
22
Nominal operating range
4 to 20 mA
Load voltage
8 V at 20 mA
Impedance
400
έ
at 20 mA
Содержание D500
Страница 82: ...82 17 Appendix Control Drawing 901305...
Страница 83: ...83...
Страница 84: ...84 17 Appendix Control Drawing 901305...
Страница 85: ...85...
Страница 86: ...86 17 Appendix Control Drawing 901305...
Страница 87: ...87...
Страница 89: ...VALVE ACCESSORIES CONTROLS 200 Jade Park Chelsea AL 35043 TEL 205 678 0507 info vacaccessories com...