14

DISPLAY

oFF

on

dEF1 dEF2 dEF3

in 1

PHOTOCELL ACTIVE ONLY DURING CLOSING

The intervention of the photocell during the
opening stage is ignored. 
The intervention of the photocell during the
closing stage causes the shutter to reopen.

PHOTOCELL ACTIVE DURING OPENING AND
CLOSING

The intervention of the photocell during the
opening phase causes the motor to stop.
When the photocell beam is released, the
automation starts during opening for the work
time set in parameter 

t i1

.

The intervention of the photocell during the
closing stage causes the shutter to reopen.

on

oFF

oFF

in 2

PHOTOCELL TEST INACTIVE

The photocell operation test is not
performed

PHOTOCELL TEST ACTIVE

Each time the control unit receives an open or
close command, the PHOTOCELL TEST verifies
that the PHOTOCELL is operating correctly.

If the test fails, the display shows 

- L5 -

oFF

oFF

oFF

in 3

MECHANICAL SAFETY EDGE

The L6 input is configured to manage a
mechanical safety edge

RESISTIVE RUBBER / OPTICAL SAFETY EDGE

The L6 input is configured to manage a safety
edge (resistive rubber / optical) with active
operation test.

If the test fails, the display shows 

- L6 -

oFF

on

oFF

in 4

FIRE FUNCTION

The L7 input is configured to manage a fire
alarm

ALARM FUNCTION

The L7 input is configured to manage an 
anti-theft command

oFF

oFF

oFF

in 5

EDGE / FIRE FUNCTION

The L6 input is configured to manage a safety
edge
The L7 input is configured to manage an alarm 

LIMIT SWITCH FUNCTION

The L6 input is configured to manage an
opening limit switch
The L6 input is configured to manage a closing
limit switch

NOTE: 

If 

in 5 

is set 

on

the settings of the 

in 3

and 

in 4

functions, they are not considered

oFF

oFF

oFF

ou 1

FLASHING LIGHT

Output (E1 - E2) is on intermittently (2 Hz) during
opening and closing and during pause mode, if
automatic reclosing is active

COURTESY LIGHT

The output (E1 - E2) is on and fixed during
opening, pause and closure. Having completed
the operating cycle, the light remains on for the
COURTESY LIGHT OFF DELAY time

oFF

on

on

ou 2

END OF CYCLE NON-ACTIVE SIGNAL 

At the end of the operating cycle, the control
unit sends no signal

END OF CYCLE ACTIVE SIGNAL

At the end of the operating cycle, the control
unit sends a signal to the WES sensors to activate
ENERGY SAVING mode

oFF

on

oFF

Lo 1

START/STOP LOGIC

The START/UP input controls the STEP or
AUTOMATIC operational cycle based on the
programmed operational logic.
The DOWN input is inactive

UP/DOWN LOGIC

The START/UP input always controls opening
and the DOWN input always controls closing,
independently of the operational logic
programmed.
UP + DOWN when pressed simultaneously is the
same as a STOP command

oFF

on

on

Lo 2

START INACTIVE WHILE OPENING

During opening, the START command
is ignored

START ACTIVE WHILE OPENING

During opening, the START command
interrupts opening (no timer is set for automatic
re-closure)

on

on

on

Lo 3

STEP LOGIC

The start command activates an
OPEN-STOP-CLOSE-STOP-OPEN
operational cycle

AUTOMATIC LOGIC

The start command activates an
OPEN-PAUSE-CLOSE-STOP operational cycle
Closure starts automatically after the pause
time set

oFF

oFF

oFF

Содержание EASY-TOP

Страница 1: ...v2home com www v2home com CENTRALE DI COMANDO DITALE PER SERRANDE AVVOLGIBILI DIGITAL CONTROL UNIT FOR ROLLER SHUTTERS ARMOIRE DE COMMANDE DIGITALE POUR STORES CUADRO DE MANIOBRAS DIGITAL PARA PERSIAN...

Страница 2: ...rules EN 12453 EN 12445 EN 12978 as well as any local rule in force Also the automation upstream electric system shall comply with the laws and rules in force and be carried out workmanlike The door t...

Страница 3: ...ENGLISH 10 ELECTRIC CONNECTIONS mWARNING Normally closed inputs STOP L2 PHOTOCELL L5 EDGE L6 FIRE L7 if not used must be bridged through the COMMON terminal L3 L8...

Страница 4: ...ordance with the following table After having made the connections power up the main control unit and adjust the power using the trimmer TR1 located on the control unit so as to obtain optimal edge op...

Страница 5: ...5B025 which besides using the keypad allows controlling the edges by radio using the special sensors see the WES EASY instructions The keypad buttons operate in parallel with the terminal controls The...

Страница 6: ...SEL keys To access the programming menu press the MENU key until the display shows in 1 To change the value of this parameter press the MENU key the display shows the currently set value on oFF Selec...

Страница 7: ...L6 input is configured to manage an opening limit switch The L6 input is configured to manage a closing limit switch NOTE If in 5 is set on the settings of the in 3 and in 4 functions they are not con...

Страница 8: ...tive safety keep the command active for 5 seconds the control unit then activates dead man mode and the shutter moves as long as the switch is held When the command is suspended the control unit retur...

Отзывы: