- 42 -
9 - SELF-LEARNING OF WORKING TIMES
This menu allows the automatic learning of the times necessary to
open and close the gate.
During this phase, the control unit memorizes also the forces
necessary to open and close the gate: these values will be
activated by using the obstacle sensor.
m
CAUTION: to perform the self-learning procedure it
is necessary to disable the ADI interface by means of the
menu
i.Adi
.
If some safeties are controlled by means of the ADI module,
they will not be active during the self-teaching stage.
m
CAUTION: ATTENTION: before proceeding, make sure
to position the mechanical stops and the limit sensors
correctly.
1.
Press and hold the
OK
key until the display shows
-APP
2.
Release the
OK
key: the display shows
ESC
(only press the
OK
key if it is desired to exit this menu)
3.
Press the
i
key: the display shows
t.LAv
4.
Press the
OK
key to activate the working time self-training
cycle: the display shows the control panel and starts the time
self-training procedure.
4.1
The gate will be activated in closing direction until the
stop end or the closing end of stroke is reached
4.2
The gate will be activated in opening direction until the
stop end or the opening end of stroke is reached
4.3
The gate will be activated in closing direction until the
stop end or the closing end of stroke is reached
m
CAUTION: during self-learning stage of times, the
motor moves at reduced speed.
5.
If the AMPEROMETRIC obstacle sensor was enabled, the
display shows the suggested value for sensor threshold.
If no operations are performed for 20 seconds, the control
unit exits the programming phase, without saving the value
recommended.
6.
The recommended value may be modified by pressing the
h
and
i
keys, and pressing the
OK
key confirms the displayed
value and the display shows
SEn.A
7.
Press and hold the
i
key until the display shows
FinE
, then
press the
OK
key, select the option
Si
and then press the
OK
key to exit programming mode, storing the value for the
sensors.
m
PLEASE NOTE: If the control unit is left to time out
from programming mode (1 minute), the obstacle sensor
return to the value that was set prior to performing self-
training (according to the default values, the sensor is
disabled).
On the other hand, the limit switch positions are always
stored.
10 - INVERTER BOARD FUNCTIONAL TEST
This menu allows you to perform a functional test on the
INVERTER board.
1.
Hold down the
OK
button until the display shows
-inv
2.
Release the
OK
button: the display shows
rEAd
3.
If the inverter board works properly after a few seconds the
display shows the firmware version of the board.
NOTE
: at this stage with the keys
h
and
i
you can access the
diagnostics menu.
Consult these menus only as directed by V2 Technical Support.
4.
Press the
OK
button: the control unit exits programming and
the display shows the control panel
5.
If the display continues to display
rEAd
, it means that the
INVERTER board is not working properly.
Refer to the V2 Technical Support.
t.LAv
5.5A
SEn.A
ESC
-APP
rEAd
-inv
Fv1.0