ENGLISH

- 37 -

4.5 - STOP

For a better safety, you can fit a stop switch that will cause the 
immediate gate stop when activated. This switch must have a 
normally close contact that will get open in case of operation.

In case the stop switch is operated while the gate is open, the 
automatic closing function will always be disabled. To close the 
gate again, you will need a start command.

Connect the stop switch cables between terminal 

M3 

and 

M4 

of 

the control unit.

The STOP switch function can be activated by means of a remote 
control stored on channel 3 of MR receiver

4.6 - PHOTOCELLS

The control unit considers two kinds of photocells, depending on
the terminal to which they are connected:

Photocell 1

Photocells installed on the gate inner side, which are active both 
during the opening and the closing phase. When photocells 1 
operate, the control unit stops the gate; as soon as the photocell 
beam is free, the control unit will open the gate completely.

m

 

WARNING: Type 1 photocells must be installed so that 

they completely cover the opening area of the gate.

Photocell 2

Photocells installed on the external gate side and which are active 
during the closing phase only. When photocells 2 operate, the 
control unit opens the gate immediately, without waiting for 
release.

PD19 control unit supplies a 24Vac power supply to photocells 
and it can perform a photocell operation test before starting the 
gate opening phase. Photocell power terminals are protected by 
an electronic fuse that stops current in case of overload.

•  Connect power supply cables of photocells transmitter 

between terminals 

M11 

and 

M12 

of the control unit.

•  Connect power supply cables of photocells receiver between 

terminals 

M10 

and 

M11 

of the control unit.

•  Connect receiver output of photocells 1 between terminals 

M5 

and 

M9 

of the control unit and receiver output of photocells 2 

between terminals 

M6 

and 

M9 

of the control unit. 

Use outputs having normally closed contact.

m

 

ATTENZIONE

:

•  If several couples of same kind photocells are mounted, their 

outputs must be connected in series.

•  In case of reflection photocells, power supply must be 

connected to terminals 

M11 

and 

M12 

of the control unit to 

carry out the operation test.

4.7 - SAFETY RIBBONS

The control unit considers two kinds of safety ribbons, depending 
on the terminal to which they are connected:

Type 1 

When type 1 safety ribbons operate during the gate opening 
phase, the control unit will close the doors for 3 seconds, then it 
stands still; when type 1 safety ribbons operate during the gate 
closing phase, the control unit will stand still immediately.  
The direction of the gate at next command of START or 
PEDESTRIAN START depends upon the parameter STOP (it inverts 
or continues the motion). 
If the input STOP is disabled, the command makes the motion
continue in the same direction.

Type 2 

when type 2 safety ribbons operate during the gate opening 
phase, the control unit will stand still immediately; when type 2 
safety ribbons operate during the gate closing, the control unit 
will open the doors for 3 seconds, then it will stand still. The 
direction of the gate at next command of START or PEDESTRIAN 
START depends upon the parameter STOP (it inverts or continues 
the motion). If the input STOP is disabled, the command makes 
the motion continue in the same direction.

Both the input can manage the classic safety edge with n.c. 
contact and the conductive rubber safety edge with 8,2 kohm
nominal resistance.

Connect type 1 safety ribbons cables between terminals 

M7 

and 

M9 

of the control unit.

Connect type 2 safety ribbons cables between terminals 

M8 

and 

M9 

of the control unit.

In order to meet the requirements of the EN12978 rules, it is 
necessary to install safety edges controlled by a control unit 
continuously checking the proper working. If using control units 
suited to the test by power outage, connect the power supply 
cables of the control unit between terminals 

M11 

and 

M12 

of the 

control unit.
Otherwise, connect them between terminals 

M10 

and 

M11

.

m

 WARNING:

•  Make use of safety ribbons having outputs with normally close 

contact.

•  Outputs of same kind safety ribbons must be connected in 

series.

4.8 - EXTERNAL AERIAL

We suggest to use the external aerial (model: ANS433) in order to 
guarantee the maximal range.

Connect the antenna hot pole to terminal 

A2 

of the control unit

and the braiding to terminal 

A1

.

Содержание AYROS series

Страница 1: ...PESO GB 230V 120V ELECTRO MECHANICAL IRREVERSIBLE RACK ACTUATOR FOR SLIDING GATES UP TO 1200 KG F OPERATEUR ELECTROMECANIQUE 230V 120V IRREVERSIBLE A CREMAILLERE POUR PORTAILS COULISSANTS JUSQU A 120...

Страница 2: ...200 mm 343 mm 178 mm 226 mm 334 mm 3 mm 328 mm 200 mm 343 mm 160 mm 74 mm 50 mm 100 mm 128 mm 206 mm 283 mm...

Страница 3: ...ITALIANO 26...

Страница 4: ...4 6 PHOTOCELLS 4 7 SAFETY RIBBONS 4 8 EXTERNAL AERIAL 4 9 ELECTRICAL CONNECTION 4 10 PLUG IN RECEIVER 4 11 ADI INTERFACE 5 CONTROL PANEL 5 1 DISPLAY 5 2 USE OF THE KEYS FOR PROGRAMMING 6 ACCESSING TH...

Страница 5: ...make any modifications to any part of the automation device or the accessories connected to it unless described in this manual Any other modifications will void the warranty on the product The instal...

Страница 6: ...are authorised for use and closure is not in a public area Examples of this type are gates inside business premises where the sole users are employees or a part of them who have been suitably informed...

Страница 7: ...tended to be installed on sliding gates to create a machine according to the provisions of the Directive 2006 42 EC The machinery must not be put into service until the final machinery into which it h...

Страница 8: ...1 7 A 2 A 2 6 A 4 3 A Running capacitor 8 F 10 F 12 F 36 F Start off capacitor 18 F 18 F 25 F 75 F Gate maximum speed 0 16 m s 0 16 m s 0 16 m s 0 18 m s Maximum thrust 400 N 670 N 950 N 950 N Duty ci...

Страница 9: ...ace and parallel to the gate 5 Wait for the complete setting of the concrete 6 Unscrew the bolts fixing the base to the clamps and put the motor on the plate 7 Adjust the 4 grains to make the motor be...

Страница 10: ...TOR Check the following points 1 the motor must be on a levelled surface and perfectly parallel to the gate 2 the distance between pinion and rack must be 1 or 2 mm If needed adjust the 4 grains 3 the...

Страница 11: ...it positions the magnet be positioned next to the magnetic sensor behind the hood as near as possible to the hood The supplied magnets have been colored differently in order to be distinguished from e...

Страница 12: ...nticlockwise closing the hatch of the lock then draw it out 4 Close the lock with the hatch J 3 6 INSTALLATION LAYOUT 1 3 E 5 4 A B F D 2 C LENGTH OF THE CABLE 10 metres from 10 to 20 metres from 20 t...

Страница 13: ...es see Strt item of programming menu mWARNING If you use maintained command devices magnetic loop detectors timers presence detectors etc clock mode must be used parameter Strt oroL Standard mode STAR...

Страница 14: ...on photocells power supply must be connected to terminals M11 and M12 of the control unit to carry out the operation test 4 7 SAFETY RIBBONS The control unit considers two kinds of safety ribbons depe...

Страница 15: ...M10 M11 M12 RECEIVER FUSE MAINS OVERLOAD L LINE N NEUTRAL LAMP 230V MAX 40W COURTESY LIGHT CONTACT START START P STOP COM PHOTO 1 PHOTO 2 EDGE 1 EDGE 2 COM 24V 10W 24V Photo Edge Test GND ANT A1 A2 mC...

Страница 16: ...uitable for a command of PD19 control unit CHANNEL 1 g START CHANNEL 2 g PEDESTRIAN START CHANNEL 3 g STOP CHANNEL 4 g COURTESY LIGHT NOTE Before programming 4 channels and function logics read carefu...

Страница 17: ...the START command pressing the i key activates the PEDESTRIAN START command There are the following three kinds of menu items Function menu Time menu Value menu Function menu setup Function menus all...

Страница 18: ...ot2 CoS1 CoS2 according to the safety devices installed on the gate For the position of the item menus inside the main menu and for the options related to each item menu refer to the chapter 12 3 Star...

Страница 19: ...o store the precise position of the range limit it is recommended to activate the slow speed near to the limit The position at which the slow speed is activated is stored as the starting point for slo...

Страница 20: ...to read the totalizing counter how to read the number of cycles before the next service is required as well as how to program the number of cycles before the next request for service as for the exampl...

Страница 21: ...e gate opens leftwards P APP Partial opening 25 0 1 00 The percentage of the path the gate performs in the case of opening using the Pedestrian Start command t PrE Pre blinking time 1 0 0 5 1 00 Befor...

Страница 22: ...pening phase This menu allows fixing the control unit conduct in case it receives a Start command during the opening phase PAUS PAUS The gate stops and goes to pause ChiU The gate immediately starts c...

Страница 23: ...ime adjustable time from 0 5 to 20 0 PA t r Pause after transit no Si In order to let the gate open for the shortest possible time it is possible to stop the gate once the passage before the photocell...

Страница 24: ...cells active both during the opening and closing phase no no Input disabled ignored by the control unit AP Ch Input enabled Fot2 Photocell 2 input This menu allows enabling the input for type 2 photoc...

Страница 25: ...sed rate below the set threshold indicates the presence of an obstacle If set to 0 the obstacle is only detected when the gate is stopped When the sensor intervenes the gate stops and is operated in t...

Страница 26: ...interrupt their beam you should hear the relay tripping Error 4 When a Start command is given and the gate does not open or does a partial opening and the following writing appears on display Err4 Th...