4 - CONTROL UNIT

PD19 is provided with a display that, not only makes 
programming simple, but also allows a continuous monitoring of 
the input statuses; in addition, thanks to a menu structure, the 
working schedule and the operation logic can be set easily.
In compliance with the European standards concerning electrical 
safety and electromagnetic compatibility (EN 60335-1,  
EN 50081-1 and EN 50082-1) it has been equipped with the low 
voltage circuit total electric insulation (motors included) from the 
network voltage.

Other characteristics:

•  Obstacle detection function

•  Automatic learning of the limit switch position

•  Tests for safety devices (photocells, safety ribbons and triac) 

before each opening

•  Deactivation of safety inputs through the configuration menu: 

no jumper is required for terminals concerning safety devices 
that have not been installed, yet. You will only need to disable 
this function from its relevant menu

•  Synchronized operation of two motors using the SYNCRO 

optional module

m

 

Installation of control unit and safety devices must

be carried out with power disconnected.

4.1 - POWER SUPPLY

The control unit must be fed by a 230V - 50Hz electric line, 
protected by a differential magnetothermal switch complying with 
the law provisions in force.

Connect power supply cables to terminals 

L

 and 

N

 of PD19 

control unit.

4.2 - FLASHING LIGHT

PD19 control unit provides for a 230V - 40W Flashing light 
equipped with intermittence inside.

Connect Flashing light cables to terminals 

B1 

and 

B2 

of the

control unit.

4.3 - COURTESY LIGHTS

Thanks to the output COURTESY LIGHT the control unit allows 
the connection of an electric appliance (e.g. courtesy light or 
garden lights), controlled automatically or by means of the special 
transmitter key.

The output COURTESY LIGHT is a simple N.O. contact with no 
power supply.

Connect the cables to terminals 

B3 

and 

B4

.

4.4 - ACTIVATION INPUTS

PD19 control unit is equipped with two activation inputs (START 
and START P.), whose operation depends on the programmed 
operation modes (see 

Strt

 item of programming menu):

m

 

WARNING: If you use maintained command devices 

(magnetic loop detectors, timers, presence detectors, etc.) 
clock mode must be used (parameter 

Strt

 = 

oroL

).

Standard mode

START = START (a command will cause the complete
opening of the gate)
START P. = PEDESTRIAN START (a command will cause the
partial opening of the gate)

Open/Close command

START = OPENING (always controls the gate opening)
START P. = CLOSING (always controls the gate closing)
This is an impulse command, that is to say that an impulse will 
cause the complete gate opening or closing.

Manned operation

START = OPENING (always controls the gate opening)
START P. = CLOSING (always controls the gate closing)
This is a monostable command, that is to say, the gate will be 
opened or closed as long as the contact is closed and it will 
immediately stop as the contact is open 

Timer mode

This feature allows you to program time slots during the day 
for the gate to be open by using an external timer or other 
maintained command devices (e.g. magnetic loop detectors or 
presence detectors). 

START = START (a command will cause the complete opening of 
the gate)
START P. = PEDESTRIAN START (a command will cause the partial 
opening of the gate)
The gate stays open (completely or partially) while the contact is 
closed on input; as soon as the contact is open the pause time 
count down will start, after which the gate will be closed again.

ATTENTION: Automatic closing must be enabled

NOTE

: If the parameter 

P.APP

 = 

0

 the timer connected to START 

P. does not cause the opening, but can inhibit the automatic 
closing at preset times.

In all modes, inputs must be connected to devices having
normally open contacts.

Connect cables of device controlling the START input between 
terminals 

M1 

(START) and 

M4 

(COM) of the control unit.

Connect cables of device controlling the START P. input between
terminals 

M2 

(START P.) and 

M4 

(COM) of the control unit.

The START input function can also be activated by pressing 

h

 key 

(outside the programming menu) or by means of a remote
control stored on channel 1 of MR receiver.

The START P. input function can also be activated by pressing 

i

 

key (outside the programming menu) or by means of a remote 
control stored on channel 2 of MR receiver.

Содержание AYROS series

Страница 1: ...PESO GB 230V 120V ELECTRO MECHANICAL IRREVERSIBLE RACK ACTUATOR FOR SLIDING GATES UP TO 1200 KG F OPERATEUR ELECTROMECANIQUE 230V 120V IRREVERSIBLE A CREMAILLERE POUR PORTAILS COULISSANTS JUSQU A 120...

Страница 2: ...200 mm 343 mm 178 mm 226 mm 334 mm 3 mm 328 mm 200 mm 343 mm 160 mm 74 mm 50 mm 100 mm 128 mm 206 mm 283 mm...

Страница 3: ...ITALIANO 26...

Страница 4: ...4 6 PHOTOCELLS 4 7 SAFETY RIBBONS 4 8 EXTERNAL AERIAL 4 9 ELECTRICAL CONNECTION 4 10 PLUG IN RECEIVER 4 11 ADI INTERFACE 5 CONTROL PANEL 5 1 DISPLAY 5 2 USE OF THE KEYS FOR PROGRAMMING 6 ACCESSING TH...

Страница 5: ...make any modifications to any part of the automation device or the accessories connected to it unless described in this manual Any other modifications will void the warranty on the product The instal...

Страница 6: ...are authorised for use and closure is not in a public area Examples of this type are gates inside business premises where the sole users are employees or a part of them who have been suitably informed...

Страница 7: ...tended to be installed on sliding gates to create a machine according to the provisions of the Directive 2006 42 EC The machinery must not be put into service until the final machinery into which it h...

Страница 8: ...1 7 A 2 A 2 6 A 4 3 A Running capacitor 8 F 10 F 12 F 36 F Start off capacitor 18 F 18 F 25 F 75 F Gate maximum speed 0 16 m s 0 16 m s 0 16 m s 0 18 m s Maximum thrust 400 N 670 N 950 N 950 N Duty ci...

Страница 9: ...ace and parallel to the gate 5 Wait for the complete setting of the concrete 6 Unscrew the bolts fixing the base to the clamps and put the motor on the plate 7 Adjust the 4 grains to make the motor be...

Страница 10: ...TOR Check the following points 1 the motor must be on a levelled surface and perfectly parallel to the gate 2 the distance between pinion and rack must be 1 or 2 mm If needed adjust the 4 grains 3 the...

Страница 11: ...it positions the magnet be positioned next to the magnetic sensor behind the hood as near as possible to the hood The supplied magnets have been colored differently in order to be distinguished from e...

Страница 12: ...nticlockwise closing the hatch of the lock then draw it out 4 Close the lock with the hatch J 3 6 INSTALLATION LAYOUT 1 3 E 5 4 A B F D 2 C LENGTH OF THE CABLE 10 metres from 10 to 20 metres from 20 t...

Страница 13: ...es see Strt item of programming menu mWARNING If you use maintained command devices magnetic loop detectors timers presence detectors etc clock mode must be used parameter Strt oroL Standard mode STAR...

Страница 14: ...on photocells power supply must be connected to terminals M11 and M12 of the control unit to carry out the operation test 4 7 SAFETY RIBBONS The control unit considers two kinds of safety ribbons depe...

Страница 15: ...M10 M11 M12 RECEIVER FUSE MAINS OVERLOAD L LINE N NEUTRAL LAMP 230V MAX 40W COURTESY LIGHT CONTACT START START P STOP COM PHOTO 1 PHOTO 2 EDGE 1 EDGE 2 COM 24V 10W 24V Photo Edge Test GND ANT A1 A2 mC...

Страница 16: ...uitable for a command of PD19 control unit CHANNEL 1 g START CHANNEL 2 g PEDESTRIAN START CHANNEL 3 g STOP CHANNEL 4 g COURTESY LIGHT NOTE Before programming 4 channels and function logics read carefu...

Страница 17: ...the START command pressing the i key activates the PEDESTRIAN START command There are the following three kinds of menu items Function menu Time menu Value menu Function menu setup Function menus all...

Страница 18: ...ot2 CoS1 CoS2 according to the safety devices installed on the gate For the position of the item menus inside the main menu and for the options related to each item menu refer to the chapter 12 3 Star...

Страница 19: ...o store the precise position of the range limit it is recommended to activate the slow speed near to the limit The position at which the slow speed is activated is stored as the starting point for slo...

Страница 20: ...to read the totalizing counter how to read the number of cycles before the next service is required as well as how to program the number of cycles before the next request for service as for the exampl...

Страница 21: ...e gate opens leftwards P APP Partial opening 25 0 1 00 The percentage of the path the gate performs in the case of opening using the Pedestrian Start command t PrE Pre blinking time 1 0 0 5 1 00 Befor...

Страница 22: ...pening phase This menu allows fixing the control unit conduct in case it receives a Start command during the opening phase PAUS PAUS The gate stops and goes to pause ChiU The gate immediately starts c...

Страница 23: ...ime adjustable time from 0 5 to 20 0 PA t r Pause after transit no Si In order to let the gate open for the shortest possible time it is possible to stop the gate once the passage before the photocell...

Страница 24: ...cells active both during the opening and closing phase no no Input disabled ignored by the control unit AP Ch Input enabled Fot2 Photocell 2 input This menu allows enabling the input for type 2 photoc...

Страница 25: ...sed rate below the set threshold indicates the presence of an obstacle If set to 0 the obstacle is only detected when the gate is stopped When the sensor intervenes the gate stops and is operated in t...

Страница 26: ...interrupt their beam you should hear the relay tripping Error 4 When a Start command is given and the gate does not open or does a partial opening and the following writing appears on display Err4 Th...

Страница 27: ...iciency of all warning devices the perfect efficiency of all safety devices measurement of the gate operating forces the lubrication of mechanical parts on the automation device where necessary the st...

Страница 28: ...ay vary depending on the intensity of use Any inspection maintenance or repairs should only be performed by qualified personnel Even if you think you know how do not modify the system and the automati...

Страница 29: ...V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY Tel 39 0172 812411 Fax 39 0172 84050 info v2home com www v2home com...

Отзывы: