8 - INSTALLATION MENÙ (

SEt

)

This menu allows you to perform the movements of the gate needed during installation. 
The automatic learning procedure enables to save run limits based on data collected by the encoder.
The manual handling procedure allows to control the gate in hold to run mode in special cases such as during installation/maintenance or
a malfunction of the photocells or edges.

m

CAUTION: ATTENTION: before proceeding, make sure to position the mechanical stops and the limit sensors correctly.

1.

Press and hold the 

OK 

key until the display shows

-SEt

2.

Release the 

OK

key: the display shows 

ESC

(only press the 

OK 

key if it is desired to exit this menu)

3.

Use the keys 

h

and 

i

to select the menu 

Mov 

to activate manual handling or 

A PPr 

to start the automatic learning 

procedure of the run limits.

4.

Press 

OK 

to start the selected procedure

8.1 - AUTOMATIC LEARNING OF THE RUN LIMITS

m

CAUTION: to perform the self-learning procedure it is necessary to disable the ADI interface by means of the menu i.Adi . 

If some safeties are controlled by means of the ADI module, they will not be active during the self-teaching stage.

5.

Press the 

OK

key to activate the working time self-training cycle: the display shows the control panel and starts the time self-training 

procedure.

5.1

The gate will be activated in closing direction until the stop end or the closing end of stroke is reached

5.2

The gate will be activated in opening direction until the stop end or the opening end of stroke is reached

5.3

The gate will be activated in closing direction until the stop end or the closing end of stroke is reached

6.

If you DO NOT have enabled the obstacle sensor (menu 

SEnS

), the self-learning procedure is completed and the display shows 

the control panel

7.

If the obstacle sensor has been enabled, the display shows the recommended value for the obstacle sensor. If no operations are 
performed for 20 seconds, the control unit exits the programming phase, without saving the value recommended.

8.

The recommended value may be modified by pressing the 

h

and 

i

keys, and pressing the 

OK

key confirms the displayed value  and the 

display shows 

SEnS

9.

Press and hold the 

i

key until the display shows 

FinE

, then press the 

OK 

key, select the option 

Si

and then press the 

OK 

key to exit 

programming mode, storing the value for the sensors.

m

PLEASE NOTE:  If the control unit is left to time out from programming mode (1 minute), the obstacle sensor return to 

the value that was set prior to performing self-training (according to the default values, the sensor is disabled). 
On the other hand, the limit switch positions are always stored.

8.2 - MANUAL HANDLING

m

WARNING: when this procedure is activated the 

safeties are not active.

5.

The display shows 

MA n

6.

Press and hold the 

h

key to open the gate or the 

i

button to close the gate

7.

Release the button to stop the gate

8.

To exit this menu, press 

OK

.

NOTE: If the motor is inactive for more than one minute the procedure terminates automatically.

Содержание ALFARISS

Страница 1: ...EUR ELECTROMECANIQUE 24V IRREVERSIBLE A CREMAILLERE POUR PORTAILS COULISSANTS JUSQU A 300 KG DE POIDS MOTOR ELECTROMECANICO 24V IRREVERSIBLES A CREMALLERA PARA PUERTAS CORREDERAS HASTA 300 KG DE PESO...

Страница 2: ......

Страница 3: ...34 4 2 ACTIVATION INPUTS 34 4 3 STOP 35 4 4 CONNECTING PHOTOCELLS 35 4 5 CONNECTING SAFETY RIBBONS 35 4 6 EXTERNAL AERIAL 36 4 7 LOW VOLTAGE LIGHT OUTPUT 36 4 8 COURTESY LIGHTS 36 4 9 POWER SUPPLY 36...

Страница 4: ...y and hazard warnings on the machinery and equipment should be complied with Electromechanical actuators for gates are not intended to be used by people including children with diminished physical sen...

Страница 5: ...t person The risk analysis should take into consideration all danger zones for the automation device which should be appropriately protected and marked In a clearly visible area apply a sign with info...

Страница 6: ...50 Idling current A 0 9 Full load current A 3 Gate maximum speed m s 0 18 Maximum thrust N 330 Duty cycle 50 Pinion M4 Z16 Working temperature C 20 55 Motor weight Kg 7 5 Protection degree IP 44 Maxim...

Страница 7: ...and parallel to the gate 5 Wait for the complete setting of the concrete 6 Unscrew the bolts fixing the base to the clamps and put the motor on the plate 7 Insert the 4 grains with their nuts in the p...

Страница 8: ...gate making sure that they stand at the same height than the motor pinion The rack MUST BE positioned 1 or 2 mm over the pinion of the motor all the gate length 3 4 INSTALLING THE MAGNETIC LIMIT SWITC...

Страница 9: ...restore the automation proceed as follows 1 Turn the key L anticlockwise until reached the limit switch then draw it out 2 Turn the key K anticlockwise closing the hatch of the lock then draw it out...

Страница 10: ...rse the connectors 4 2 ACTIVATION INPUTS PD13 control unit is equipped with two activation inputs START and START P whose operation depends on the programmed operation modes see Strtitem of programmin...

Страница 11: ...control unit Use outputs having normally closed contact mSAFETY RIBBONS INSTRUCTIONS If several edges with normally closed contacts are used the outputs should be connected in series If several conduc...

Страница 12: ...VER PD13 control unit is suitable for plugging in a MRx receiver having a high sensitivity super heterodyne architecture MRx module receiver is provided with 4 channels and each of them is suitable fo...

Страница 13: ...ing traditional devices with N O contact J2 Pedestrian open command for connecting traditional devices with N O contact J3 STOP command N C contact J4 Common J5 Photocell 1 xterior N C contact J6 Phot...

Страница 14: ...explored by using the 3 keys h i and OK located on the side of the control unit display PLEASE NOTE Outside the configuration menu pressing the h key activates the START command pressing the i key ac...

Страница 15: ...ges which will get lost 7 LOADING THE DEFAULT PARAMETERS dEF If necessary it is possible to restore all parameters to their standard or default values see the final summary table m PLEASE NOTE This pr...

Страница 16: ...ached 5 2 The gate will be activated in opening direction until the stop end or the opening end of stroke is reached 5 3 The gate will be activated in closing direction until the stop end or the closi...

Страница 17: ...cell edge limit switches or encoder To start the emergency dead man operating mode activate the start command START for 3 seconds Note if the Strt parameter is set as StAn the Start command from the t...

Страница 18: ...eys you can alternate the display of thousands or units Area 2 is the reading of the number of cycles before the next request for service its value is rounded down to the hundreds Area 3 is the setup...

Страница 19: ...unction This function is useful for reducing the energy consumption of the automation device while in stand by mode If the function is enabled the control unit will enter ENERGY SAVING mode under the...

Страница 20: ...y of the obstacle sensor When the current absorbed by the motor exceeds the value set the control unit detects an alarm rA AP Slow down in opening 1 5 0 1 00 This menu allows regulating the percentage...

Страница 21: ...the pause If the photocell operates during the opening time this time will be immediately stored as pause time This function allows having a fast closing as soon as transit through the gate is comple...

Страница 22: ...rol unit ProS The input STOP stops the gate pressing the command START the gate continues the motion invE The command STOP stops the gate at the next START the gate starts moving in the opposite direc...

Страница 23: ...reshold indicates the presence of an obstacle If set to 0 the obstacle is only detected when the gate is stopped When the sensor intervenes the gate stops and is operated in the reverse direction for...

Страница 24: ...ed section 4 4 Error 4 When a Start command is given and the gate does not open or does a partial opening and the display shows Err4 It means that the end of stroke is damaged or that the wiring that...

Страница 25: ...com 14 MAINTENANCE Maintenance should be performed in full compliance with the safety instructions described in this manual and in accordance with current legal and regulatory provisions The recommend...

Страница 26: ...ENGLISH 50...

Страница 27: ...months for normal domestic use but this period may vary depending on the intensity of use Any inspection maintenance or repairs should only be performed by qualified personnel Even if you think you kn...

Страница 28: ...ENGLISH 52...

Страница 29: ......

Отзывы: