ENGLISH
- 49 -
Error 3
When a Start command is given and the gate does not open and
the following writing appears on display
Err3
It means that the photocell test failed.
1.
Be sure that no obstacle interrupted the photocell beam when
the Start command was given.
2.
Be sure that photocells, as enabled by their relevant menus,
have been installed actually.
3.
If you have photocells 2, be sure that
Fot2
menu item is on
CF.Ch
.
4.
Be sure that photocells are powered and working; when you
interrupt their beam, you should hear the relay tripping.
Error 4
When a Start command is given and the gate does not open (or
does a partial opening) and the following writing appears on
display
Err4
This anomaly can occur when in one of the following conditions:
1.
If a START command is sent with the motor released.
2.
During the self-learning cycle if there are any problems with
the range limits.
Check the direction of the magnets, if they are backwards,
they should be removed and inverted.
If the magnets are installed correctly, it means that the limit
switch sensor is damaged or the cabling connecting the sensor
to the central control unit is broken/damaged.
Change the end of stroke sensor or the broken wiring.
3.
During normal operation. If the error persists send the control
unit to V2 S.p.A. for repair.
Error 5
Once given a start control, the gate does not open and the
display shows
Err5
It means that the test of the safety edges failed.
Check that the menu of the test of safety edges (Co.tE) have been
set correctly.
Check that the safety edges enabled from the menu are installed.
Error 6
During the manoeuvre the motor stops and the display shows
Err6
It means that there are communication problems with the
inverter board. If the problem persists, the control unit must be
sent to V2 SpA for repair.
Error 7
When given a start control the gate does not open and the display
shows
Err7
This indicates an error in the encoders’ operation.
Encoder malfunction or broken connection.
Error 8
When executing a self-learning function, one of the following
conditions occurs:
1.
the control is refused and the display shows
Err8
It means that the setting of the control unit is not compatible
with the requested function.
In order to carry out self-learning, the Start inputs must be
enabled in standard mode (
Strt
menu set to
StAn
) and the
ADI interface must be disabled (
i.Adi
menu set to
no
).
2.
The procedure stops and the displays shows
Err8
It means that a safety device has tripped.
Error 9
When you are trying to change the control unit setups and the
following writing appears on display
Err9
It means that programming was locked by means of the
programming lock key CL1+ (code 161213).
To change the settings it is necessary to insert in the connector of
the ADI interface the same key used to activate the programming
lock, and unlock the device.
Error 10
When a start command is given, the gate does not open and the
display shows the message
Er 10
This means that the ADI module function test failed
Error 12
When a Start command is given and the gate does not open (or
does a partial opening) and the following writing appears on
display
Er I2
This means the motor overheating protection has tripped.
The system will start working again as soon as the motor has
cooled.