DISPLAY
DATI
DESCRIZIONI
DEFAULT
MEMO
DATI
St.rt
Operation modes
StAn
no
- Start inputs from terminal board are disabled
StAn
- Standard operation
AP.CH
- Separated opening and closing commands
PrES
- Manned operation
oroL
- Timer operation
FrEn
no / Si
Brake function
no
StoP
STOP input
no
no
- STOP input not available
invE
- STOP command stops the gate: START command starts moving in the opposite direction
ProS
- STOP command stops the gate: pressing the START command gate continues the motion
Fot 1
PHOTO 1 input
APCH
APCh
- Input is available for the connection of the photocell
no
- Not available
Fot 2
PHOTO 2 input
CFCh
CFCh
- Photocell is active in closing and also when the gate is still
no
- Not available
Ch
- Photocell is active during the closing
Ft.tE
no/Si
Photocell operational test
no
CoS1
no/Si
Border 1 input (fixed border)
no
CoS2
no/Si
Border 2 input (mobile border)
no
FC.En
no/Si
End of stroke inputs
Si
ASM
0.5” ÷ 3.0”
Anti-skid function
0.5”
no
- Function disabled
SEnS
0 ÷ 10
Obstacle sensor level
5
Cont
Counter viewing
tot
tot.
- Total number of completed cycles (views in thousands or in units)
Man
- Number of cycles before the next request for service (such a number has been
rounded off to hundreds and it can be set up on 1000-step; in case it is set up
on 0, the request will be disabled and no will be viewed)
APPr
Automatic learning of the operation time
no
no
- Function disabled
Go
- Start up of the automatic learning procedure
FinE
End of programming
no
no
- It does not exit from the program menu
Si
- It exits from the program menu by storing the setup parameters