OPERATION PANEL
There are 4 buttons on the panel:
(1) “ESC”, exit and return ;
(2) “ ”, back to the front page and data increasing;
(3) “ ”
,
to the next page and data decreasing;
(4) “ENT”, enter.
LCD SCREEN
Figure 23 Operation panel
fault
Run
Warn
Fault
Inverter stand-by. The public grid fault(A001, A003,
A004, A005or A006);
Yellow indicator blinks in every 0.5s, others off
Run
Warn
Fault
(1) Inverter stand-by. Temperature abnormal(E006);
(2) Recoverable Inverter stand-by. DC input fault
(E001);
Yellow indicator keeps on, others off
Unrecoverable
fault
Run
Warn
Fault
Hardware or software fault (E003, E004, E005, E008,
E009, E011, E013 or E015). De-couple the inverter from
the system before maintenance.
Red indicator blinks in every 0.5s, others off
Run
Warn
Fault
Current-leakage or unqualified output power energy of
the inverter (E007, E010, E014, E017, E018 or E020).
De-couple the inverter from the system before
maintenance.
Red indicator keeps on, others off
Artificial turned
off
Run
Warn
Fault
Stop after the communication or panel command. All
indicators are on.
Note
Please refer to detailed fault information and troubleshooting for more info.