Run Param
Run Param
UV volt 1
UV time 1
OV volt 1
OV time 1
UF Freq 1
UF time 1
ACUV Volt(phase volt)
115V
ACUV Time
00.04s
309V
00.02s
ACUF Frequency
47.99Hz
00.12s
50.50hz
00.12s
·
Input Password
0000
196V
252V
0.19s
01.90s
49.49Hz
595s
50.2Hz
115s
Run Restart Time
060s
Island protect:on
OFF
ON
ACOV Volt(phase volt)
ACOV Time
ACUF Time
ACOF Frequency
ACOF Time
ACUV Volt(phase volt)
ACUV Time
ACOV Volt(phase volt)
ACOV Time
ACUF Frequency
ACUF Time
ACOF Frequency
ACOF Time
There are 2 protections under
G83/G59(UK) and PEA(Thailand)
standards, and there is only one
protection under other grid tied
standard.
Set ACUV Volt, ACUV time and others
under the related submenus, and
then press “
” and “
” to modify,
and finally press “ENT” to confirm.
Generally, it is only necessary to set
ACUV2, ACOV2 and ACUF2 value for
ACUV, ACOV and ACUF protection.
And it is necessary to set ACOF1 and
ACOF2 together for ACOF protection.