. Fault diagnosis and solutions

 

 

 

The inverter is easy to maintain. When you encounter the following problems, please refer to the 

Solutions  below,  and  contact  the  local  distributor  if  the  problem  remains  unsolved.  The  following 
table  lists  some  of  the  basic problems  that  may  occur  during  the  actual  operation  as well  as their 
corresponding basic solutions.

 

 

 

 

 

 

Fault diagnosis table

 

 

 

Content

 

 

Codes

 

 

Explaination

 

 

Solutions

 

 

 

 

Di

s

c

hgOverCur

 

 

 

 

00

 

Battery discharge over 
current. When the battery 
is loaded, the load is too 
large.

 

(1) Nothing need to do, Wait one minute for 
the inverter to restart.

 

(2) Check whether the load is in compliance 
with the specification.

 

(3) Cut off all the power and shut down all the 
inverter; disconnect the load and plug in to 
restart inverter, then check.

 

 

 

 

 

O

v

e

Load

 

 

 

 

 

01

 

The load power is greater 
than other power(PV,BAT).

 

(1) Check whether the load is in compliance

 

with the maximum power of the inverter.

 

(2) Cut off all the power and shut down all the 
inverter; disconnect the load and plug in to 
restart inverter, then check whether the load 
is short circuited if the fault has been 
eliminated.

 

(3) Contact customer service if error warning 
continues.

 

 

 

B

a

tDi

sc

onnect

 

 

 

02

 

Battery  Disconnect. 
(Battery  voltage  not 
identified)

 

(1) Check whether the battery is connected. 
(2) Check if battery wiring port is open 
circuited.

 

(3) Contact customer service if error warning 
continues.

 

 

 

 

Bat Under Vol

 

 

 

 

03

 

Battery voltage lower than 
normal range.

 

(1) Checking System Settings, If so, power off 
and restart.

 

(2) Check if the grid power down. If so 
waitingfor the grid power up, the inverter will 
automatically charge.

 

(3) Contact customer service if error warning 
continues.

 

 

 

Bat L

o

c

a

pacit

 

 

 

04

 

Bat Low capacity

 

(1) Battery Low that setting capacity. 
(SOC<100%-DOD)

 

 

 

 

Ba

t Ove

r Vo

l

 

 

 

 

05

 

The battery voltage is over 
than the Inverter maximum 
voltage.

 

(1) Checking System Settings, If so, power off 
and restart.

 

(2) Contact customer service if error warning 
continues.

 

Содержание VT-66036103

Страница 1: ...another query please contact our dealer or local vendor from whom you have purchased the product They are trained and ready to serve you at the best Multi Language Manual QR CODE Please scan the QR co...

Страница 2: ...ll supply power to the nearby grid when the voltage loss is happened in the power system It is dangerous for maintenance personnel and the public X1 Hybrid series inverter provide Active Frequency Dri...

Страница 3: ...al Damage 09 3 2 Packing List 09 3 3 Tools required for installation 09 3 4 Mounting 10 4 Electrical Connection 11 4 1 Grid connection and EPS connection 11 4 2 PV connection 13 4 3 Battery Connection...

Страница 4: ...d here Otherwise may result in a risk of re electric shock or injury to person Make sure that existing wiring is in good condition and that wire is not undersized Do not disassemble any parts of inver...

Страница 5: ...of high voltages Danger indicates a hazardous situation which if not avoided will result in death or serious injury Danger Risk of electric shock Observe enclosed documentation The inverter can not b...

Страница 6: ...provide power for emergency use during the grid lost by using the energy from battery and inverter generated from PV In addition the parallel function is available o grid mode System Diagram 1 applies...

Страница 7: ...o the loads as rst priority if solar energy is not su cient to power all connected loads battery energy and solar energy will supply power to the loads at the same time PV Inverter Grid Work modes Pea...

Страница 8: ...nergy will charge battery as rst priority if solar energy is excess the excess power will supply load If solar energy is not BAT EPS Inverter Grid BAT EPS su cient to charge battery and supply loads g...

Страница 9: ...rnal WiFi L Reserved port G DRM BMS H Grid current DRY IO M USB port for upgrading N POWER CAN LEAD NTC I Pressure valve O EPS output P Grid output Note 1 The Update port For on premises upgrades 2 Th...

Страница 10: ...HDI 2 Load control optional AC input Nominal AC power VA 3680 5000 6000 Rated grid voltage range V 230 176 to 270 Rated grid frequency Hz 50 60 Nominal AC current A 16 21 7 26 Max AC current A 16 21 7...

Страница 11: ...3W Over Voltage Category l MAINS PV Battery Pollution Degree II cooling Natural Noise level 40dB Inverter Topology non isolated Active anti islanding method Power variation Communication interface CA...

Страница 12: ...t please check the accessories rst The packing list shown as below A B C D E F G H I Object Description A Inverter B Bracket C Expansion screws and pan head screws D PV connectors 2 positive 2 negativ...

Страница 13: ...ll holes with driller make sure the holes are deep enough at least 60mm to support the inverter 1 3 Install the expansion tubes in the holes and tighten them Then install the wall bracket with the exp...

Страница 14: ...on and EPS connection Hybrid inverter are designed for single phase grid Voltage is 220 230 240V frequency is 50 60Hz Other technical requests should comply with the requirement of the local public gr...

Страница 15: ...t 60mm of conductor material sectional area and remove 10mm of insulation from the end of wire 3 3 Separate the docking screw cap of the AC terminal from the housing portion and insert stripped wires...

Страница 16: ...s voltage range please comply with electric safety rules when connecting Please do not make PV positive or negative ground Connection Steps Step1 Checking PV module to ensure PV is in open circuit sta...

Страница 17: ...e at least 4AWG 4 The battery communication can only work when the battery BMS is compatible with the inverter 5 To replace the battery you need to turn o all switches and unplug the system communicat...

Страница 18: ...of the crystal head conforms to the 568B standard orange white orange green white blue blue white green brown white and brown 1 8 PIN 1 2 3 4 5 6 7 8 CAN De nition X X X BMS_CANH BMS_CANL X X X Rs485...

Страница 19: ...o COM port at the bottom of the inverter Step2 Build the connection between the inverter and router Step3 Create a user account online Please check the WiFi user manual for more details Diagram Could...

Страница 20: ...verter is in Warning Off The inverter has no Inverter Warning E lit in red The inverter is in fault status Off The inverter has no errors F Function Button Esc Return from current interface or functio...

Страница 21: ...18 5 3 Instructions for the use of three modes 485 WORK MODE REMOTE CTRL PEAK SHIFT Test mode Test mode DC SOURCE Lithum 48V 14 AUTO TEST Italian cer tification...

Страница 22: ...face Press Enter button Choose according to local power grid Default password 00000 Press UP DOWN button Adjust the figure Press Enter button 3 GRID STD PVinput mode Enter password Setting 1 SYS SETTI...

Страница 23: ...V Settings and explanations are provided in section 5 5 4 6 SYSTEM1 STATE SELF CSM GRID US CA PV I P PARALL 5 4 3 System setting2 Interface Description SYSTEM2 BMS Com CAN Anti Reve DISA DOD 80 BMS Co...

Страница 24: ...y status C Indicates that the battery is rechargeable From the BMS D Indicates that the battery can discharge From the BMS F The battery requests a forcible charge From the BMS BATTERY VOLT 300V CURR...

Страница 25: ...time current FREQ INV real time frequency INV VOLT 0 0V CURR 0 00A FREQ 0 00Hz 5 4 13 LOAD Interface Description VOLT LOAD real time voltage CURR LOAD real time current PERCENT LOAD real time percent...

Страница 26: ...ystem information Display complete machine status information including initialization standby PV grid connection grid connection of battery hybrid power supply fault service self check o grid grid IN...

Страница 27: ...number press the Enter key to move the cursor forward and press the Esc key move the cursor backward PASSWORD INPUT XXXXX 5 5 3 Setup Interface Description This interface is used for various informat...

Страница 28: ...ITY WORKTIME 1 TIME 1 2 TIME 2 3 TIME 3 CHAG START1 00 00 CHARGE END100 02 DISC START1 00 03 DISCHA END1 23 59 This interface is used to select the working mode Press ESC button return to setting inte...

Страница 29: ...it only when the battery is too low WAKE UP EN 1 DISABLE 2 ENABLE 5 5 4 4 REMOTE CTRL Interface Description Remote control the inverter on or o Subsequent support The default option is disabled REMOTE...

Страница 30: ...TYPE Interface Description This interface is used to select battery type Press Up Down button to move corresponding options Press Enter button to enter the selected menu Select the LEAD ACID enter bu...

Страница 31: ...ty setting will a ect the maximu charging current for example set 100Ah the maximum charging current is 100A 0 2 20A 5 5 5 2 BAT COMM Interface Description This interface is used to select battery com...

Страница 32: ...X 7 FAC MIN 8 FAC MAX 9 ACTIVE REP 5 5 7 2 REACT MODE Interface Description RUN SETTING 1 REACT MODE 2 GRID POWER 3 DISC POWER REACT MODE 1 POWER FACTOR 2 REACT POWER 3 QU WAVE 4 QP WAVE POWER FACTOR...

Страница 33: ...ISC PERCENT INPUT 100 5 5 7 5 PV POWER Interface Description The input value is power percent of PV PV PERCENT INPUT 100 5 5 7 6 VAC MIN Interface Description The input value of Grid low voltage It e...

Страница 34: ...10 ACTIVE REF Interface Description This interface is used to select active reference Press Up Down button to move corresponding options Press Enter button to enter the selected menu Each menu have en...

Страница 35: ...AGE Interface Description This interface is used to select language LANGUAGE 1 Chinese 2 English 5 5 11 BACKLIGHT 5 5 11 1 BACKLIGHT Interface Description This interface is used to set light time LIGH...

Страница 36: ...D Interface Description This interface is used to set password PASSWORD OLD XXXXX NEW XXXXX CONFIRM XXXXX 5 5 15 MAINTENANCE 5 5 15 1 MAINTENANCE Interface Description This interface is used to enter...

Страница 37: ...interface INQUIRE 1 INV MODULE 2 MODULE SN 3 FIRMWARE 4 RECORD 5 DIAGNOSE 5 6 1 1 INV MODULE Interface Description This interface show inverter model MODEL 12K 5 6 2 MODULE SN Interface Description Th...

Страница 38: ...tie statistic 2 Inverter Grid connection times statistic 3 Displays power peak in history and for the day 4 Displays statistic for the day KWH 5 Displays statistic for the month KWH 6 Displays statis...

Страница 39: ...ing 59 S2 Test 59 S2 OK Wait Wait Testing 27 S1 Wait Test 27 S1 OK Wait Testing 27 S2 Wait Test 27 S2 OK Wait Testing 81 S1 Wait Test 81 S1 OK Wait Testing 81 S2 Wait Test 81 S2 OK Wait Testing 81 S1...

Страница 40: ...h the test results Press the up down button to page through the test results Press the up down button to page through the test results Press the up down button to page through the test results Object...

Страница 41: ...is in compliance with the maximum power of the inverter 2 Cut o all the power and shut down all the inverter disconnect the load and plug in to restart inverter then check whether the load is short ci...

Страница 42: ...US voltage is over maximum value 1 Check the input mode setting is correct 2 Restart the inverter and wait until it functions normally Inv over cur 15 The inverter current exceeds the normal value 1 R...

Страница 43: ...ning continues Bus soft fail 32 The inverter may be damaged 1 Restart the inverter and wait until it functions normally 2 Contact customer service if error warning continues Inv soft fail 33 BUS short...

Страница 44: ...V1 4...

Отзывы: