VG-6132 Gas Extinguishing Panel
7
Fig. 5-2
Pressing “Enter ” key, the cursor can move up and down to set delay time. Pressing “▼” key, delay time will be
added 1.
Pressing “Enter” key saves the delay time.
Then pressing “Cancel” key returns to the loop check.
5.1.3 Loop-checking Set
Pressing “Menu” key and “▼” key, choose “7 Loop check”. Press “Enter” key to go to the screen for setting
number of loop-check, as shown in Fig. 5-2.
Fig. 5-2
Pressing “▼” key, the number of Loop-check will be added 1.
Pressing “Enter” key saves the set.
Pressing “Cancel” returns to system operation page.
5.1.4 Printer Set
Press “Menu” key, enter the password and then press “▼” key, choose “8 Printer Set”. Press “Enter” key to go to
the screen for setting printer, as shown in Fig. 5-2.
Fig. 5-3
Press “▼” key, the printer can be set to ON or OFF states.
Press “Enter” key to save the set.
Press “Cancel” to return to system operation page.
5.2 System Operation
LCD of the system displays time as shown in Fig. 6-1 after power on.
Fig. 6-1
The First Lineindicates the system time.
The Second Lineindicates that there is no fire and fault message.
The First line indicates the system time.
The Second LinThat there is short or open circuit in Zone 2. Please view details by entering Fault Query menu.
08: 23: 15
System Operation On
Polling Coil No: 05
Printer Off
08: 23: 15
Circuit Fault
In Zone 2
08: 23: 15
Fire In Zone 2