VG-6132 Gas Extinguishing Panel
8
The First Line indicates the system time.
The Second Linethat there is fire alarm message in Zone 2.
5.3 Self-test
Pressing “Self-test” key
,
and then “Enter” key four times, the system begins self-testing. All LEDs of the system
are lit, the buzzer gives continuous alarm sound and LCD display “self-testing…”.
5.4 Reset
Pressing “Reset ” key, and then “▲” key four times, the system is reset.
5.5 Silence
Pressing Silence key when there is fire or fault, sound of the control panel can be silenced.
5.6 Records
5.6.1 Fault records
In system operation page, press Menu, and input “▲▼▲▼” password. Pressing “▼” can enter the screen
shown in Fig. 6-2. Then press “Enter” to go to “Fault query”. Press “▼” to display fault messages. It returns to
fire condition if there is a fire.
Fig. 6-2
5.6.2 History Record
In system operation page, press “Menu” and press “▼” to enter the screen shown as Fig. 6-3. Then pressing
“Enter” goes to “History Record Query”. Press “▼” to display history records. This panel can record 999
messages.
Fig. 6-3
5.7 Start and stop sounder strobe
When there is fire, the souder strobe is activated automatically. When there is not fire, press Menu to enter the
password, and then press “▼” and “Enter” to start the sounder strobe. If the sounder strobe should be stopped,
repeate the previous steps and then press Enter to stop.
5.8 Switch between manual and auto
Warning
:
The right side of the display is auto-switching and special function area. Please don’t operate it
unless you are special trained person, in order to avoid property loss and personal injuries.
Fault Record
History Record