Level limit switch
Series VN 1000 / 2000 / 5000 / 6000
Technical information / Instruction manual
page
Signal output
Electronic
modules:
Universal voltage
(Relay SPDT and DPDT)
3-wire
PNP
2-wire
without contact
8/16mA
NAMUR
(IEC 60947-5-6)
FSL/ FSH or Characteristic Setting
Remark: „FSH/ FSL“ is used for electronic modules:
Universal voltage, 3-wire, 2-wire
"Characteritic" is used for electronic module:
NAMUR
If the sensor is used to indicate full load, set to
Fail Safe High or Falling Characteristic.
Power failure or line break is regarded as „full“
signal (protection against overcharging).
If the sensor is used to indicate empty load, set to
Fail Safe Low or Rising Characteristic. Power
failure or line break is regarded as „empty“
signal (protection against running dry).
LED „Signal output“
Setting FSL/ FSH or Characteristic
Signal output
Setting
Relay SPDT
Relay DPDT
3-wire PNP
2-wire without contact
8/16mA
LED „Signal output“
Setting
NAMUR
IEC 60947-5-6
LED „Signal output“
Electronic module
Signal output
Vibranivo
®
1
2
3
4
5
6
7
8
9
10
11
12
VN 1000 / 2000 / 5000 / 6000 g
gi180713
23
FSL
FSH
FSL
FSH
FSH
FSL