Level limit switch
Series RF 3000
Technical Information / Instruction manual
page
Display
Explanation
Menu item
A. FSH *
FSL
Fail Safe High
Fail Safe Low
Signal output, Fail safe setting
B. ALL *
C-U
U-C
Covered probe <-> Uncovered probe
Covered probe -> Uncovered probe
Uncovered probe -> Covered probe
Signal output, Delay direction
C. 0,5 *
2
5
to 60
seconds
Signal output, Delay time
Adjustable in steps (increment is 5 seconds)
D. 0,5
1
2 **
4
10
15
25
35
pF
Sensitivity
Required capacitance increase between uncovered probe (after
calibration) and switch to output "covered probe".
Change presetted value only if required by the application, see
calibration guide on page 25.
Note: Menu item D is not valid and will not bee shown on the
display, if Manual calibration (Menu item G) is set to ON.
*
Factory setting
** Standard Factory setting is 2 pF. Optional other setting is present (depending on order)
Quickstart menu
• When the unit is in Measurement mode, press MENU button for 3 sec to enter in Quickstart menu.
Note: If "Code" is displayed, a Lock Code is required. Set the code number with the arrow buttons and confirm with
the Menu button. Then press again the Menu button for 3 sec to enter in Quickstart menu.
• Press for 3 sec to return to Measurement mode.
• Press for <1 sec to store setted value and jump to next menu item.
• If no button is pressed within ca 5min, the unit returns to the measurement mode (timeout). All changed menu settings
will be stored.
• Arrow buttons increase/ decrease the value to be setted
Quickstart
FSH/ FSL Setting
FSH: Set as full detector. Power failure or line break is stated as "full" signal (protection against overcharging).
FSL: Set as empty detector. Power failure or line break is stated as "empty" signal (protection against dry running).
Setting
Signal output
Relay DPDT
LED
yellow
green
green
yellow
power failure
uncovered
probe
covered
probe
Note: Red LED is blinking during Menu setting
RFnivo
®
1
2
3
4
5
6
7
8
9
10
11
12
RF 3000 f
gi241014