NivoGuide® 8100 • Two-wire 4 … 20 mA/HART
3 Mounting
61266-EN-190215
3 Mounting
3.1 General instructions for use of the instrument
Protect your instrument against moisture ingress through the following
measures:
•
Use a suitable connection cable (see chapter "
Connecting to
power supply
")
•
Tighten the cable gland or plug connector
•
À½ÆÅÇÍÆÌÁÆ¿ÀÇÊÁÒÇÆ̹ÄÄÑƓÌÍÊÆÌÀ½ÀÇÍËÁÆ¿ËÇÌÀ¹ÌÌÀ½»¹ºÄ½
gland or plug connector point downward
•
Lead the connection cable downward in front of the cable entry or
plug connector.
This applies mainly to outdoor installations, in areas where high
ÀÍÅÁ¼ÁÌÑÁ˽ÐȽ»Ì½¼Ƽ½Ɩ¿ƖÌÀÊÇÍ¿À»Ä½¹ÆÁÆ¿ÈÊÇ»½Ë˽Ëƽ¹Æ¼ÇÆ»ÇÇĽ¼
or heated vessels.
To maintain the housing protection, make sure that the housing lid is
closed during operation and locked, if necessary.
¹Ã½ËÍʽÌÀ¹ÌÌÀ½¼½¿Ê½½Ç¾»ÇÆ̹ÅÁƹÌÁÇÆËȽ»ÁŲ½¼ÁÆ»À¹È̽Ê
"
Technical data
ͷŽ½ÌËÌÀ½½ÐÁËÌÁÆ¿¹ÅºÁ½ÆÌ»ÇƼÁÌÁÇÆËƖ
3.2 Mounting
instructions
Mount NivoGuide 8100 in such a way that the distance to vessel
installations or to the vessel wall is at least 300 mm (12 in). In non-
metallic vessels, the distance to the vessel wall should be at least
500 mm (19.7 in).
During operation, the probe must not touch any installations or the
vessel wall. If necessary, fasten the probe end.
In vessels with conical bottom it can be advantageous to mount the
sensor in the center of the vessel, as measurement is then possible
nearly down to the lowest point of the bottom. Keep in mind that
measurement all the way down to the tip of the probe may not be pos-
ËÁºÄ½ƖÀ½½Ð¹»ÌιÄͽǾÌÀ½ÅÁÆƖ¼ÁË̹ƻ½ƼÄÇϽʼ½¹¼º¹Æ¼ƽÁËË̹̽¼
in chapter "
Technical data
" of the operating instructions.
Fig. 2: Vessel with conical bottom
Plastic vessel/Glass vessel
The guided microwave principle requires a metallic surface on the
ÈÊÇ»½ËËŲÌÌÁÆ¿ƖÀ½Ê½¾ÇʽƓÁÆÈĹËÌÁ»Î½Ë˽ÄËƓ½Ì»ƖƓÍ˽¹ÆÁÆËÌÊÍ
-
Protection against mois-
ture
Installation position
Type of vessel