24
Example:
To add 2 additional 90 degree elbows to a 3” pipe for a 75 boiler.
Each elbow is 3 additional feet per 90 degree elbow for a total of 6 feet.
(1 elbow @ 3 feet + 1 elbow @ 3 feet = 6 additional feet of pipe)
The total additional pipe is then subtracted from the maximum allowable pipe length to give the new maximum length of 94
feet with 6, 90 degree elbows.
(“TOTAL EQUIVALENT LENGTH”):
Original 100 feet max. - 6 feet for 2 additional elbows = new 94 feet maximum length.
The first 5 feet of “TOTAL EQUIVALENT LENGTH” of vent
piping run must be CPVC:
The length of pipe is counted from the boiler jacket (air intake
pipe) or from vent tee (vent pipe) the termination is not
counted toward the “Total Equivalent Length”.
For additional elbows, reduce the maximum vent length as
shown:
• 2” 90 degree elbow -1 ½ feet per additional elbow.
• 3” 90 degree elbow - 3 feet per additional elbow.
coMBUstioN air aND VeNt PiPiNG leNGtHs
Boiler
siZe
2” PIPE MINIMUM
VENTING
2” PIPE MAXIMUM
VENTING”
3” PIPE MINIMUM
VENTING
3” PIPE MAXIMUM
VENTING”
100
8 FEET
21 FEET
27 FEET
92 FEET
75 & 50
8 FEET
26 FEET
32 FEET
112 FEET
COMBUSTION AIR AND VENT PIPE
Combustion air and vent piping to be pitched back to boil-
5.
er at minimum ¼” per foot from intake and vent terminals
so that all moisture in combustion air and vent piping
drains to boiler. Pipes must be pitched continuously with
no sags or low spots where moisture can accumulate and
block the flow of air or flue gas. Combustion air and vent
pipes must be airtight and watertight.
Combustion air and vent piping lengths:
4.
Содержание UB100
Страница 15: ...15 Near Boiler Piping Figure 2 Single Zone Boiler Piping ...
Страница 16: ...16 Figure 3 Multi zone Boiler Piping With Zone Valves Near Boiler Piping ...
Страница 19: ...19 Figure 6 Diaphragm Type Expansion Tank Piping Near Boiler Piping ...
Страница 20: ...20 Figure 7 Conventional closed type Expansion Tank Piping Near Boiler Piping ...
Страница 27: ...27 Combustion Air and Vent Pipe Figure 11 Combustion Air and Vent Piping ...
Страница 32: ...32 Electrical Wiring Figure 13 Field Wiring Connections ...
Страница 53: ...53 DETAILED SEQUENCE OF OPERATION ...
Страница 57: ...57 TROUBLESHOOTING CHART 2 TROUBLESHOOTING ...
Страница 58: ...58 TROUBLESHOOTING CHART 3 TROUBLESHOOTING ...
Страница 60: ...60 TROUBLESHOOTING CHART 5 TROUBLESHOOTING ...
Страница 63: ...REPAIR PARTS Model No UB90 50 UB90 75 UB90 100 UB90 50 100 GAS FIRED DIRECT VENT CONDENSING HOT WATER Boiler ...
Страница 64: ...64 20 3 5 TYP OF 4 6 11 8 9 10 13 15 16 2 12 1 21 17 18 18 4 19 7 A Jacket and Base Assembly Repair Parts ...
Страница 72: ...P O Box 4729 Utica NY 13504 4729 ...