15
WARNING
Fire, explosion, and asphyxiation hazard. Improper
installation could result in death or serious
injury. Read these instructions and understand all
requirements before beginning installation.
!
•
This boiler requires a dedicated direct vent system.
•
Vent connections serving appliances vented by natural draft
shall not be connected into any portion of mechanical draft
systems operating under positive pressure.
•
Use only manufacturer approved venting materials or
venting materials primer and glue approved to: ULC S636
in Canada, or UL 1738 in the U.S.
•
Materials used in the U.S. shall comply with Authority
having jurisdiction and in absence of such with: ANSI/ASTM
D1785, ANSI/ASTM F441, ANSI/ASTM F493.
•
Vent system must have unrestricted movement through
walls, ceilings and roof penetrations.
•
Check for proper joint construction when joining pipe to fittings.
•
If vent is penetrating ceilings and floors, openings must
have means of fire stopping in joist areas and proper fire-
stop spacer assemblies installed.
•
Standard roof flashing methods must be used to install roof
flashing.
•
Frame wall and roof openings to provide support for
attachment of termination assemblies.
•
Support piping in accordance with pipe manufacturer's
instruction and authority having jurisdiction. In absence
of manufacturer's instruction use pipe hooks, pipe straps,
brackets, or hangers of adequate and strength located
at intervals of 3 ft (1 m) or less. Allow for expansion/
contraction of pipe.
•
Venting shall be supported adjacent to each joint using
steel strapping or equivalent.
See Figure 5-1.
WARNING
ABS/PVC venting shall not to be used this product.
Use of DWV plumbing pipes to vent this boiler shall be
prohibited.
Use of cellular core PVC (ASTM F891), cellular core
CPVC, or Radel® (polyphenolsulfone) in venting
systems shall be prohibited.
Covering non-metallic vent pipe and fittings with
thermal insulation shall be prohibited.
Failure to follow these instructions could result in death
or serious injury.
!
5 - COMBUSTION AIR AND VENT PIPING
NOTICE
Follow venting manufacturer's equivalent lengths for
specialty fittings.
•
Support horizontal sections of vent pipe to prevent sags
capable of accumulating condensate.
•
Assemble vent materials in accordance with venting
manufacturer’s instructions.
•
Slope exhaust pipe minimum of 1/4” per foot, or vent
manufacturer’s recommendation, whichever is greater;
back toward the boiler.
•
Any "in line" elbows in flue system must be taken into
consideration. First elbow on the top of the boiler is
included in equivalent length calculations.
•
Use U.V. stabilized polypropylene when it will be exposed
to sunlight, wind, or prone to freeze ups.
•
Manufacturer requires use of an approved mechanical
fastener, which may vary per vent pipe manufacturer, at
every push-fit gasket connection when using a single wall
polypropylene vent system.
5.2 Removal of Existing Boiler From Common Vent
System
When existing boiler is removed from common venting
system, common venting system is likely to be too large for
proper venting of appliances remaining connected to it.
After removal of existing boiler, following steps shall be
followed with each appliance remaining connected to common
venting system placed in operation, while other appliances
remaining connected to common venting system are not in
operation:
•
Seal any unused openings in common venting system.
•
Visually inspect venting system for proper size and
horizontal pitch. Determine there is no blockage or
restrictions, leakage, corrosion and other deficiencies which
could cause an unsafe condition.
•
When practical, close all building doors, windows, and
all doors between space in which appliances remaining
connected to common venting system are located and
other spaces of building. Turn on clothes dryer and any
appliance not connected to common venting system.
Turn on exhaust fans, such as range hoods and bathroom
exhaust so they will operate at maximum speed. Do not
operate summer exhaust fan. Close fireplace dampers.
•
Turn on appliance being inspected. Follow lighting
instructions. Adjust thermostat so appliances will operate
continuously.
•
Test for spillage at draft hood relief opening after 5
minutes of main burner operation. Use flame of match or
candle, smoke from cigarette, cigar or pipe.
• Determine each appliance remaining connected to common
venting system properly vents when tested as outlined
above. Then return doors, windows, exhaust fans and any
other gas-burning appliance to their previous condition of
use.
•
Any improper operation of common venting system should
be corrected so installation conforms with National Fuel
Code, ANSI Z223.1/NFPA 54 and/or Natural Gas and Propane
Installation Code, CAN/CSA B149.1. When re-sizing any
portion of common venting system, common venting system
should be re-sized to approach minimum size as determined
using appropriate tables in Chapter 13 of the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 and/or Natural Gas and
Propane Installation Code, CAN/CSA B149.1.
5.1 General
•
Installations shall comply with Authority having jurisdiction
and in absence of such with:
»
U.S. ANSI Z223.1 /NFPA 54 in the United States
»
CSA B149.1 in Canada.
240012874 REV A, [01/31/2020]
Содержание MACF-150
Страница 63: ...61 A 1 MODELS 125 Heat Only APPENDIX A WIRING DIAGRAMS 240012874 REV A 01 31 2020 ...
Страница 64: ...62 APPENDIX A WIRING DIAGRAMS A 2 MODELS 165 Heat Only 240012874 REV A 01 31 2020 ...
Страница 65: ...63 A 2 MODELS 150 Combi APPENDIX A WIRING DIAGRAMS 240012874 REV A 01 31 2020 ...
Страница 66: ...64 A 4 MODELS 205 Combi APPENDIX A WIRING DIAGRAMS 240012874 REV A 01 31 2020 ...
Страница 67: ...65 NOTES 240012874 REV A 01 31 2020 ...
Страница 68: ...66 NOTES 240012874 REV A 01 31 2020 ...
Страница 90: ...20 150F 205F WITH ZONE PUMPS WIRING DIAGRAM 150F 205F WITH ZONE PUMPS PN 240012875 REV A 01 31 2020 ...
Страница 92: ...22 150F 205F WITH ZONE VALVES WIRING DIAGRAM 150F 205F WITH ZONE VALVES PN 240012875 REV A 01 31 2020 ...
Страница 98: ...28 MODEL 125F Heat Only 125F FLOOR STANDING HEAT ONLY WIRING DIAGRAM PN 240012875 REV A 01 31 2020 ...
Страница 99: ...29 MODEL 150F Combi 150F FLOOR STANDING COMBI WIRING DIAGRAM PN 240012875 REV A 01 31 2020 ...
Страница 100: ...30 165F FLOOR STANDING HEAT ONLY WIRING DIAGRAM MODEL 165F Heat Only PN 240012875 REV A 01 31 2020 ...
Страница 101: ...31 205F FLOOR STANDING COMBI WIRING DIAGRAM MODEL 205F Combi PN 240012875 REV A 01 31 2020 ...
Страница 106: ...36 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240012875 REV A 01 31 2020 ...
Страница 114: ...44 NOTES PN 240012875 REV A 01 31 2020 ...