13
4.1 Boiler Location Considerations
•
Ambient room temperature always above 32°F (0°C) to
prevent freezing of liquid condensate.
•
Approved for installation in closets or alcove provided
it is correctly designed for that purpose and minimum
clearances are met.
•
Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during operation and
service (circulator replacement, condensate trap,
control replacement, etc.).
• Access to outdoors to meet minimum and maximum
pipe lengths for combustion air and vent piping. See
section 6.
•
Disposal of condensate. See section 6.
•
Drainage of water (or water - antifreeze solution)
during boiler service or from safety relief valve
discharge. See section 5.
•
Access to system water piping, gas supply, and
electrical service. See sections 5, 7 and 8.
•
Clearances to combustible materials and service
clearances. See Table 1 and Figures pg. 11.
•
Room-sealed boiler installed in a room containing bath
or shower shall be installed so person using bath or
shower cannot touch any electrical switch or boiler
control utilizing line voltage electricity.
•
Multiple Boilers can be placed side by side, or back to
back.
•
Observe service clearances in all installations.
•
For Direct Vent installations, air vents are not required
in room boiler is installed in, or when installed in closet
or compartment.
WARNING
Fire Hazard! Do not install on carpeting. Failure to
follow these instructions could result in death or
serious injury.
!
4 - LOCATING BOILER
4.2 Floor Location
• Place crated boiler as close to selected location as
possible and uncrate boiler. Boiler may be moved into
position with appliance dolly or (2) two wheel hand
truck. Insert dolly or hand truck under left hand side of
boiler. It is possible to slide boiler for short distance on
smooth floor or surface.
•
Adjust the position of the boiler verify it is level and
plumb.
•
Select level location central to piping systems served
and as close to vent and air intake terminals as
possible.
•
Accessibility clearances, if more stringent (i.e. larger
clearances) than required fire protection clearances,
must be used for boiler installation. Accessibility
clearances may be achieved with the use of removable
walls or partitions.
•
Boiler is approved for installation in closets and
on combustible floors.
This boiler shall NOT be
installed on carpeting.
•
Install equipment in location which facilitates operation
of venting and combustion air intake piping systems as
described in this manual.
•
Advise owner to keep venting and combustion air
intake passages free of obstructions. Both venting
and combustion air intake piping systems connected
to outdoors must permit flow through piping systems
without restrictions for boiler operation.
•
Keep boiler area clean of debris and free of flammable
and combustible materials, vapors and liquids.
WARNING
Fire hazard. Do not install boiler on combustible
flooring or carpeting. Failure to follow these instructions
could result in death or serious injury.
!
WARNING
Fire, explosion, and asphyxiation hazard. Improper
installation could result in death or serious
injury. Read these instructions and understand all
requirements before beginning installation.
!
240012874 REV A, [01/31/2020]
Содержание MACF-150
Страница 63: ...61 A 1 MODELS 125 Heat Only APPENDIX A WIRING DIAGRAMS 240012874 REV A 01 31 2020 ...
Страница 64: ...62 APPENDIX A WIRING DIAGRAMS A 2 MODELS 165 Heat Only 240012874 REV A 01 31 2020 ...
Страница 65: ...63 A 2 MODELS 150 Combi APPENDIX A WIRING DIAGRAMS 240012874 REV A 01 31 2020 ...
Страница 66: ...64 A 4 MODELS 205 Combi APPENDIX A WIRING DIAGRAMS 240012874 REV A 01 31 2020 ...
Страница 67: ...65 NOTES 240012874 REV A 01 31 2020 ...
Страница 68: ...66 NOTES 240012874 REV A 01 31 2020 ...
Страница 90: ...20 150F 205F WITH ZONE PUMPS WIRING DIAGRAM 150F 205F WITH ZONE PUMPS PN 240012875 REV A 01 31 2020 ...
Страница 92: ...22 150F 205F WITH ZONE VALVES WIRING DIAGRAM 150F 205F WITH ZONE VALVES PN 240012875 REV A 01 31 2020 ...
Страница 98: ...28 MODEL 125F Heat Only 125F FLOOR STANDING HEAT ONLY WIRING DIAGRAM PN 240012875 REV A 01 31 2020 ...
Страница 99: ...29 MODEL 150F Combi 150F FLOOR STANDING COMBI WIRING DIAGRAM PN 240012875 REV A 01 31 2020 ...
Страница 100: ...30 165F FLOOR STANDING HEAT ONLY WIRING DIAGRAM MODEL 165F Heat Only PN 240012875 REV A 01 31 2020 ...
Страница 101: ...31 205F FLOOR STANDING COMBI WIRING DIAGRAM MODEL 205F Combi PN 240012875 REV A 01 31 2020 ...
Страница 106: ...36 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240012875 REV A 01 31 2020 ...
Страница 114: ...44 NOTES PN 240012875 REV A 01 31 2020 ...