39
DS1083-135
LINE TERMINATION SETTINGS (Z)
Refer to the previous chapter for correct Z line termination settings.
Default settings
All door phones are con
fi
gured by default with line termination on.
All brackets are con
fi
gured by default with line termination on.
All distributors are con
fi
gured by default with line termination off.
All column interfaces are con
fi
gured by default with line termination on (jumper between Z terminal
present).
The line terminal on/off jumper (Z) is not present on some video door phones (e.g. 1750/1, 1750/5, 1750/6,
1750/15, 1750/16 and 1760/6).
In this manner, in the typical case of system with calling station connected directly to the power supply unit
and apartment stations connected as
fl
oor extensions to a column, only the jumper of the termination of the
last distributor needs to be changed to the ON position.
2Voice column
power supply
unit
TC
12
2
1
Termination ON
DEVICE CONFIGURATION
The con
fi
guration can be made also when the system is not powered because dip-switches on the door unit
and apartment stations and interface columns are used.
Particular care must be devoted to setting the device codes.
CALLING STATION CONFIGURATION
The calling stations in the system must be univocally identi
fi
ed according to the type. The following
explanation concerns the door unit with buttons mod. Sinthesi. Refer to the corresponding instruction
booklet for other door unit types, e.g. Alpha calling station or calling modules.
ID
:
door unit identi
fi
cation
Set a number from 0 to 3 if the door unit is a main unit or from 0 to 31 if the door unit is a secondary unit as
shown in the following
fi
gure.
There must not be two main stations with the same ID. Two secondary stations may coexist with the
same ID but with different address (0 or 1).
The ID of the secondary door unit must coincide with the column ID set on the column distributor 1083/53
or column interface 1083/50, if present.
APARTMENT STATION CONFIGURATION
The following explanations concern Miro video door phone, for other apartment stations see their
instruction manual.
CODE
: user code.
Set a number from 0 to 126 according to the following rules:
No two apartments in the system must have the same user code.
Apartment stations in parallel in the same apartment must have the same user code.
User codes on the same backbone be must consecutive
.
•
•
•
•
•