![UPS ZINTO A 1000 Скачать руководство пользователя страница 88](http://html.mh-extra.com/html/ups/zinto-a-1000/zinto-a-1000_user-manual_1061330088.webp)
To install the emergency power off, please proceed as follows:
1.) Switch off UPS system.
2.) Remove connector from the emergency power off terminal
block. For this purpose first undo the two outer screws.
3.) Connect the connections on the connector removed to a
floating normally open contact. (Rating: max. 60V DC /
30V AC, 20mA). Use a cable with a cable cross-section of
0.3mm²
–
0.75mm² for the connection.
ock for
intentional
disconnection by fixing with the two screws.
the UPS
system can be started.
pen contact again.
4.) Fit configured connector back in the terminal bl
emergency power off, lock secure against un
5.) To switch on the UPS system, ensure the floating normally
open contact from step 3.) is deactivated. Then
6.) To test the emergency power off, activate the normally
open contact.
7.) Re-start by deactivating the normally o
88 / 181
Manual-ZintoA_final_ger_engl_it_20090929.doc
30.09.2009, Dipl.-Ing. S. Spitzley
Содержание ZINTO A 1000
Страница 2: ...2 181 Manual ZintoA_final_ger_engl_it_20090929 doc 30 09 2009 Dipl Ing S Spitzley ...
Страница 62: ...62 181 Manual ZintoA_final_ger_engl_it_20090929 doc 30 09 2009 Dipl Ing S Spitzley ...
Страница 64: ...64 181 Manual ZintoA_final_ger_engl_it_20090929 doc 30 09 2009 Dipl Ing S Spitzley ...
Страница 122: ...122 181 Manual ZintoA_final_ger_engl_it_20090929 doc 30 09 2009 Dipl Ing S Spitzley ...