background image

UE-12Li80

3. Test Condition

3.1 Standard Test Conditions

3.1.1 Unless otherwise specified, all performance tests is required conducted at temperature 25°C±2°C,                   
         Humidity less than 45% ~ 75% RH.
3.1.2 Unless otherwise specified, the tested product is required unused within two month after outgoing.

NO.

Items

Description 

Length: 318±0.5mm

Width:   165±0.5mm

Height:  215±0.5mm

Dimension

Self-discharge rate

Operating Temperature 

Approx: 12.3±0.6Kg 

Charging

0~45°C

Residual capacity

≤3%/month; ≤15%/years

16

17

18

Weight

Discharging

-20~60°C

Recommended operating temperature

15°C~35°C

Reversible capacity

≤1.5%/month; ≤8%/years

Storage Temperature & Humidity Range

Less than 1 month

-20°C~35°C

45% RH~75

% 

RH 

19

Less than 3 months

-10°C~35°C

45% RH~75

% 

RH 

Recommended storage environment

:

15°C~35°C

45% RH~75

% 

RH

15

Long time storage: 
If the battery need be stored for a long time, the voltage should be 13.2V (50% SOC), and stored in the condi-
tion as storage proposal. It need at least one charge & discharge cycle every six months

01

01

01

02

www.upowerbatteries.com

66A Tzar Asen Srt.
Sofia, Republic of Bulgary
Tel. (+34) 918 021 649
Fax. (+34) 917 750 542
[email protected]

Содержание Ecoline UE-12Li80

Страница 1: ...h Rated Capacity Minimum Capacity Energy Floating charge voltage Internal resistance Limited charge voltage 12 8V 12 8V 13 8 0 2V 2 3 4 5 7 8 Nominal Voltage Outgoing Voltage 30mΩ 14 6 0 2V Standard charge current 50A 9 Maximum charge current 80A 10 Standard discharge current 80A 11 Maximum discharge current 100A withstand 30min Battery initial Temp 25 5 C 12 Pulse discharge current Withstand the ...

Страница 2: ... 3 month 15 years 16 17 18 Weight Discharging 20 60 C Recommended operating temperature 15 C 35 C Reversible capacity 1 5 month 8 years Storage Temperature Humidity Range Less than 1 month 20 C 35 C 45 RH 75 RH 19 Less than 3 months 10 C 35 C 45 RH 75 RH Recommended storage environment 15 C 35 C 45 RH 75 RH 15 Long time storage If the battery need be stored for a long time the voltage should be 13...

Страница 3: ... Charge Retention ability Residual capacity 80 Internal resistance 30mΩ 50 battery SOC state frequency of 1 KHZ ac resistan ce tester Discharge with the current of 0 33C until it can t discharge and then rest it for 1h Charge the battery following CC 0 33C CV 14 6V mode to full capacity and then rest it for 1h Repeat above process until full charged capacity is no more than 80 of normal value Accu...

Страница 4: ...y temperature Charge over temperature Protection 65 5 C Discharge over temperature Release 48 10 C Protection 65 5 C Release 48 10 C Short circuit Do not short circuit the electrodes Designed For 550A 800A 500us MOSFET over temperature Protection 100 5 C Release 70 15 C 01 01 01 04 www upowerbatteries com 66A Tzar Asen Srt Sofia Republic of Bulgary Tel 34 918 021 649 Fax 34 917 750 542 info upower...

Страница 5: ...with metal Avoid excessive physical shock or vibration don t hit fall stamp on the battery Without the permission of the manufacturer and guidance forbidden to remove or to assemble the battery Do not use the battery mixed with other different manufacturer type or model batteries Keep the battery against high temperature Otherwise it will cause battery heat get into fire or lose some function and ...

Страница 6: ...use for a long time because of its own self discharge characteristics can also cause discharge to prevent the occurrence of a discharge battery should maintain a certain capacity maintain the voltage at 50 state of SOC 10 Other Chemical Reaction Because batteries utilize a chemical reaction battery performance will deteriorate over time even if stored for a long period of time without being used I...

Отзывы: