48V100Ah - Energy Storage Lithium Battery Module - User Manual

3.7 

Setting the Battery Address: After the preceding operations are complete, set the IP address of the battery 

connected to the inverter to 1, and set other IP addresses from 2 until all the Settings are complete.

Note:

 The address of the battery must not be the same. Otherwise, communication will be affected.

3.8 

Check that all connections are correct and firm.

3.9 

Start the inverter to charge the battery. In normal state, all the batteries will be activated and enter the working

mode.

 

4.1  Preliminary determination steps: 

The battery can be turned on, but red light is lighting, and cannot charge or discharge. If the red light is lighting, that 
means system is abnormal, please check values as following: 

Temperature:

 Above 55

º

C or under -20

º

C, the battery could not work.

Solution: to move battery to the normal operating temperature range between -20

º

C and 55

º

C. 

Current:

 If current is greater than 110A, battery protection will turn on.

Solution: Check whether current is too large or not, if it is, to change the settings on power supply side. 

High Voltage

: If charging voltage above 54V, battery protection will turn on.

Solution: Check whether voltage is too high or not, if it is, to change the settings on power supply side.  

Low Voltage

: When the battery discharges to 44.5V or less, battery protection will turn on.

Solution: Charge the battery for some time, the red light turn off. Excluding the four points above, if the faulty is still 
cannot be located, turn off power switch of the battery and repair. 

4.2 The battery cannot be charged or discharged. 

4.2.1 

No charging: First check that the charging voltage of the charging device is normal, if the charging voltage is 

normal (52.5V-54.75)V), and then use the upper computer to connect with the battery, read the detailed data of the 
battery, check whether the voltage and temperature of the single battery are normal, if the charging equipment is 
normal, the general reason for not charging is: the single charging over voltage protection or high temperature 
protection. 

4.2.2 

Fail to discharge: Disconnect the battery from the load and measure whether the voltage of the battery is 

normal, If the battery has no output voltage, press the Reset button to sleep the battery first and then wake up 
(restart the battery), and test the battery voltage again. If the battery voltage returns to normal, it indicates that the 
battery is protected, Check the load.

4. Trouble Shooting Steps 

Paseo de Extremadura, 39 - 28935 Móstoles - Madrid (Spain)

Tel. +34 918 021 649 - Fax. +34 917 750 542

[email protected]

www.masterbattery.es/en

Содержание UE48LI100-3U

Страница 1: ...Information Version 1 0 48V100Ah LFP Product Energy Storage Lithium Battery Module User Manual...

Страница 2: ...s State RUN light green LED ashing to show the battery running status RUN Alarm light The red LED blinks to indicate that the battery is alarming and the red LED blinks to indicate that the battery is...

Страница 3: ...in hibernation state press the button for 3 seconds and release it BMS will be activated and the battery will return to normal working mode 2 Manual sleep When the battery is in the normal working sta...

Страница 4: ...When the batteries are in parallel address 1 is the host and other addresses are slave The battery at address 1 is connected to the inverter If the address is 0 it is in single battery mode For detail...

Страница 5: ...address 2 05 48V100Ah Energy Storage Lithium Battery Module User Manual Schematic diagram of battery parallel installation Note The battery should be turned off during installation After installation...

Страница 6: ...idental electric shock or short circuits If insulated tools are not available cover the entire exposed metal surfaces of the available tools except their tips with electrical tape When installing batt...

Страница 7: ...terminal of the inverter DC input to the negative terminal of the battery 3 4 Connect the positive wires Connect all the positive terminals of the battery Finally connect the positive terminal of the...

Страница 8: ...verter This end connects to the Remote Box of the inverter This port connects to the RS485 port of the battery Note This communication line should be connected with attention to the direction Paseo de...

Страница 9: ...is too high or not if it is to change the settings on power supply side Low Voltage When the battery discharges to 44 5V or less battery protection will turn on Solution Charge the battery for some ti...

Страница 10: ...ul substances such as electrolytes wash it thoroughly with soap and water immediately If you feel unwell seek medical attention immediately 5 2 If smoke or open ame is found in the battery use only a...