7 Technical data
7.1 Technical specifications
Description
Value
IP
IP30 (IP: degree of inaccessibility
to active parts of the product and
degree of water)
Max. ambient RH (relative
humidity)
60 % at 20 °C
Marking
CE, UKCA
ERP
Class I
Power supply
230 V AC, 50 Hz
Operating temperature
0 °C to +50 °C
Wired control
TRIAC 230 V
Storage temperature
-20 °C to +60 °C
Room temperature sensor (rt)
CTN 10 K at 25 °C
External temperature sensor
CTN 10 K at 25 °C
Thermostat colour
Thermostat body RAL 9016
Transparent front glass
Directive 2014/35/EU (LVD)
Harmonised standards applicable under Directive 2014/35/EU for
Low Voltage (LVD):
•
EN 60730-1:2017 Safety ― Automatic electrical controls for
household and similar use - Part 1: General requirements
•
EN 60730-2-9:2013 Safety ― Automatic electrical controls for
household and similar use - Part 2-9: Particular requirements for
temperature sensing controls
Directive 2014/30/EU (EMC)
Harmonised standards under Directive 2014/30/EU for
Electromagnetic compatibility (EMC):
•
EN IEC 61000-3-2:2019 ― Electromagnetic compatibility (EMC)
- Part 3-2: Limits - Limits for harmonic current emissions
(equipment input current 16 A per phase)
•
EN IEC 61000-3-3:2013 + AMD1:2017 ― Electromagnetic
compatibility (EMC) - Part 3-3: Limits - Limitation of voltage
changes, voltage fluctuations and flicker in public low-voltage
supply systems, for equipment with rated current =16 A
Declaration of conformity
Usable in all Europe
Declaration of conformity
We hereby declare under our own responsibility that products dealt with
by these instructions satisfy all essential demands linked to the
information stated in the Safety instruction booklet.
7.2 Dimensions
85 mm
60 mm
85 mm
22 mm
ZD0000060
7.3 Wiring diagram
WD0000047
Item
Connection
Description
A
L
Power
B
L out
Actuator
C
N
Neutral
D
External sensor
E
External sensor
16
|
Uponor Base thermostat display T-27 230V
|
Installation and operation manual