System
Issue
Cause
Resolution
Pump is turning on when
there is no demand
The system is running the pump in "Exercise" mode.
• No action is required.
System not switching
between Comfort and ECO
mode
More than one Comfort/ECO switch is connected to
the system (to the GPI).
• Select one GPI switch and uninstall the others
(only one switch in the system is supported).
High supply temperature
(This alarm only displays
if Supply Diagnostics is
enabled in the Smatrix
Pulse App.)
The supply temperature is too high.
• Check the heat source or supply temperature
controller to lower the supply temperature.
• Contact the installer if the problem persists.
Low supply temperature
(This alarm only displays
if Supply Diagnostics is
enabled in the Smatrix
Pulse App.)
The supply temperature is too low.
• Check the heat source or supply temperature
controller to increase the supply temperature.
• Other potential causes may be too low flow on
the supply line or a malfunctioning circulation
pump.
• Contact the installer if the problem persists.
Loop is warm even after an
extended period without
heat call
The actuator(s) are not closing.
• Contact the installer.
• Check that the actuator is installed correctly.
• Replace the actuator.
The actuator(s) may still be in the initial factory
default position (partially open).
• Adjust setpoint temporarily to maximum
setting so the actuators fully open (channel
LED is red) to deactivate the default position.
• Manually cycle the actuator.
Low average temperature
Thermostat setpoints are too low.
• Increase the setpoints on the thermostats in
the rooms where the average temperature is
calculated.
The supply temperature is too low.
• Check the heat source or supply temperature
controller to increase the supply temperature.
• Other possible causes may be too low flow on
the supply line or a malfunctioning circulation
pump.
• Contact the installer if the problem persists.
The average temperature limit is too low.
• Increase the average temperature limit.
A window or door is open.
• Close any windows or doors that might affect
the measured temperature.
Содержание Smatrix Base PULSE
Страница 1: ...Smatrix Pulse Installation and Operation Manual...
Страница 8: ...6 l Smatrix Pulse Installation and Operation Manual...
Страница 16: ...14 l Smatrix Pulse Installation and Operation Manual...
Страница 22: ...20 l Smatrix Pulse Installation and Operation Manual...
Страница 28: ...26 l Smatrix Pulse Installation and Operation Manual...
Страница 40: ...38 l Smatrix Pulse Installation and Operation Manual...
Страница 42: ...40 l Smatrix Pulse Installation and Operation Manual...
Страница 60: ...Notes 58 l Smatrix Pulse Installation and Operation Manual...
Страница 61: ...Notes uponor com l 59...