Sequence of Operation

Mode Button Operation

Pressing the Mode button selects the 
operation of the thermostat to be  
either Heating, Cooling, or Off. The 
thermostat must be configured for  
heat/cool/fan operation in order for  
the cooling operation to be available.

Heating Operation

Heating is available when the Mode is set 
to Heat. To change the heat temperature 
setting, push the   or   button to select 
a preferred temperature setting for the 
current schedule time period. The Heat  
On symbol is shown on the display when  
the thermostat is heating.

To change the temperatures for the  
other time periods, enter the Set Temp 
menu by pressing both the 

 and 

 

buttons together, press Menu to locate  
the Set Temp menu, and press PRGM to 
enter the menu.

Hydronic Systems 

When operating a hydronic  
radiant floor, baseboard or radiator  
heating system, the thermostat uses 
Pulse Width Modulation (PWM)  
operation and cycles the heat on and  
off /- 1.5°F (1°C) of the  
temperature setting.

Forced Air Systems 

When operating a forced air heating  
system, the thermostat uses a 
differential of +/- 0.7°F (0.4°C).

Temperature Sensor Location 

The thermostat can operate the  
heating system based upon either an air 
temperature sensor, a floor temperature 
sensor, or a combination of both the air 
and floor temperature sensors together. 

Air Temperature Only 

If there is only an air temperature  
sensor (no floor sensor), the thermostat 
maintains the desired air temperature. 

Floor Temperature Only 

If the air sensor has been disabled, 
the thermostat will only maintain floor 
temperature and ignore air temperature. 
This operation is recommended for areas 
such as bathrooms to ensure that tile 
floors are warm to the touch.

Floor and Air Temperature 

If the air sensor is turned on and a floor 
sensor is connected, the thermostat will 
maintain the desired air temperature as 
well as a minimum floor temperature.

This operation is recommended for areas 
with large windows that allow the sun 
to shine into a room and keep it warm 
without the need for heat. This can 
allow the floors to cool off during the 
afternoon. When the sun goes down, it 
can take a long time for the floors to get 
warm again. This may cause the room to 
cool off too much in the early evening. 
A floor minimum setting can help with 
this condition by maintaining a floor 
minimum temperature. Keep in mind the 
floor minimum temperature will override 
the air temperature, and if set too high,  
may overheat the room.

22

uponorpro.com

Содержание SetPoint 521

Страница 1: ...SetPoint 521 Programmable Thermostat with Floor Sensor Installation and Operation Manual INSTALLATION AND OPERATION MANUAL RADIANT HEATING SYSTEMS PR OGRAMM ABLE TH ER MOST AT...

Страница 2: ...638 9517 uponorpro com 2015 Uponor All rights reserved Second Edition First Printing January 2015 Printed in Canada Uponor has used reasonable efforts in collecting preparing and providing quality in...

Страница 3: ...r from overheating and enhance comfort The programmable schedule supports either a 7 day or 24 hour schedule with 2 or 4 events per day A permanent temperature hold button overrides the programmable s...

Страница 4: ...12 Switch Settings 13 User Interface 14 Programmable Settings 14 Fan Menu 15 Set Temperature Menu 16 Time Menu 17 Schedule Menu 18 Setup Menu 19 Sequence of Operation 22 Mode Button Operation 22 Heat...

Страница 5: ...do so voids the warranty Radio Frequency Interference The installer must ensure this control and its wiring are isolated and or shielded from strong sources of electromagnetic noise Conversely this C...

Страница 6: ...other cause for inaccurate temperature readings Away from equipment appliances or other sources of electrical interference Easy access for wiring viewing and adjusting the display screen Approximatel...

Страница 7: ...stat front onto the thermostat base 3 1 4 83 mm Stud Gang Box Thermostat Front Thermostat Base Adapter Plate A3040012 Mounting Directly to the Wall 1 Drill holes and install the wall anchors 2 Feed th...

Страница 8: ...ck Floor Coverings greater than 3 8 10 mm If installing a thick floor covering directly to the subfloor cut a groove 1 8 4 mm wide by 1 16 2 mm deep into the back of the flooring material to accommoda...

Страница 9: ...ide by 3 16 5 mm deep by 13 4 45 mm long into the insulation to accommodate the sensor Place the sensor in the groove and sandwich the sensor between the insulation and the subfloor Use a suitable fas...

Страница 10: ...emperature using the thermometer Disconnect the S1 or S2 and Com wires from the thermostat Using an electrical meter measure the resistance of the S1 or S2 and Com wires at the thermostat location Usi...

Страница 11: ...13 17 436 60 16 15 311 65 18 13 474 70 21 11 883 75 24 10 501 80 27 9 299 85 29 8 250 Temperature Resistance F C 90 32 7 334 95 35 6 532 100 38 5 828 105 41 5 210 110 43 4 665 115 46 4 184 120 49 3 76...

Страница 12: ...4 V R W H N X X H N H N N H Com Switching Relay Zone 1 Zone 2 Zone 3 Class 2 Transformer R W Zone 1 Zone 2 Zone 3 Pump N L Switching Relay Thermostat Wiring T T C N L R C R Y W2 Rc G G Rh W1 S1 S2 Com...

Страница 13: ...2 Com No Power R W G Field Jumper Required Rc to G Air Conditioner R Y G C R Y W2 Rc G G Rh W1 S1 S2 Com No Power Air Conditioner Field Jumper Required Rc to G C R Y W2 Rc G G Rh W1 S1 S2 Com No Power...

Страница 14: ...does not flash Max if using a floor sensor 5 When the Heat On symbol appears on the display use an electrical meter to check for voltage on the W1 and C wires connected to the zone valve wiring cente...

Страница 15: ...ed and the access level may be changed Go to the Setup menu to change the access level Set to Unlock during the installation process 2 ON H C F Thermostat is configured to operate one stage heating on...

Страница 16: ...ecome the MENU button Press the MENU button to change from one menu to the next 3 While in the Programming Menus the HOLD button changes function to become the PRGM program button Press the PRGM butto...

Страница 17: ...turned on Fan The fan is turned on Mode Heat The heating system is allowed to operate Mode Cool The cooling system is allowed to operate Mode Off The heating and cooling systems are off Sun Schedule o...

Страница 18: ...emperature for the event Access Level Installer User Range 50 to 100 F 10 0 to 38 0 C Conditions Room Sensor On or Sensor 1 or 2 is set to Room and Schedule is set to On Default 85 F 29 5 C Setting Di...

Страница 19: ...vel Installer User Range Sunday to Saturday Conditions Always available Default Sunday Time Mode Select either 12 or 24 hour time format Access Level Installer User Range 12 or 24 hour Conditions Alwa...

Страница 20: ...time period of the day The temperature settings are used during this time period Sa Fr Th We Tu Mo Su Access Level Installer User Range 12 00AMto11 50PM SKIPor 00 00 to 23 50 SKIP Conditions Schedule...

Страница 21: ...our 7 Day Select either a 24 hour or a 7 day repeatable schedule Access Level Installer User Range 24 hour or 7 day Conditions Schedule setting is set to On Default 24 hour Optimum Start Select whethe...

Страница 22: ...UTO ON Conditions Always available Default AUTO Type Device Type number Hold the button to view the software version Access Level Installer User Range 521 Conditions Always available Default 521 Senso...

Страница 23: ...he Set Heat setpoint at which the second stage heat can turn on Access Level Installer User Range 1 5 to 8 0 F 1 5 to 8 0 C Conditions Available when switch setting 2 is set to 1H or 2H and W2 Relay i...

Страница 24: ...operate the heating system based upon either an air temperature sensor a floor temperature sensor or a combination of both the air and floor temperature sensors together Air Temperature Only If there...

Страница 25: ...ning Freeze protection for garages This operation is also recommended for rooms with hardwood floors Setting floor minimum and maximum temperatures is a way of enhancing the comfort of the living spac...

Страница 26: ...t to On to allow air circulation through the building This is useful if the air in the room is stale or if circulating cool air from a basement throughout a home can reduce the temperature in the uppe...

Страница 27: ...edule to skip a temperature change and remain at the previous temperature setting The SKIP setting can be found between 11 50 p m 23 50 hours and 12 00 a m 0 00 hours Optimum Start When a programmable...

Страница 28: ...r cooling Permanent Hold The thermostat includes a Hold button When the Hold button is pressed the thermostat stops operating based on the programmable schedule and the hold temperature can be set usi...

Страница 29: ...or Heat Cool Includes Sensor 079 Control Microprocessor control This is not a safety limit control Packaged weight 0 6 lb 290 g Dimensions 311 16 H x 3 W x 15 16 D 94 x 76 x 24 mm Enclosure White PVC...

Страница 30: ...ck for loose or damaged wires Locate and repair the problem as described in the Sensor Testing section of this brochure The error clears after the auxiliary sensor fault is corrected If the auxiliary...

Страница 31: ...29 SetPoint 521 Programmable Thermostat Installation and Operation Manual...

Страница 32: ...l 800 321 4739 Fax 952 891 2008 Uponor Ltd 2000 Argentia Rd Plaza 1 Ste 200 Mississauga ON L5N 1W1 CANADA Tel 888 994 7726 Fax 800 638 9517 SetPoint521_A3040521_InstOpManual_68503_1115 Copyright 2015...

Отзывы: