background image

½" to 2" adapter installation

1.  Assemble the joint by inserting the 

pipe into the adapter until it meets 
the pipe stop. Note that you can use 
clean water to ease the assembly 
process. Wetting the pipe and/or the 
adapter will ease the pipe-insertion 
process. Be sure to check the pipe 
insertion depth using the reference 
mark on the pipe’s outside diameter. 
(See step 5 in the previous Prepress 
section on 

page 5

.) 

 

Important! 

Only press the adapter 

when the pipe is fully inserted into 
the adapter.

2.  Using the correct size press jaws  

in the press tool, place the jaws 
over the bead on the adapter. 
Ensure the press tool and jaws 
remain perpendicular to the pipe’s 
centerline.

3.  Press the tool’s trigger or actuation 

button to begin the press cycle. 
The cycle is complete when the 
jaw fully encloses the mouth 
of the adapter. Once the cycle 
is complete, release the jaws 
from around the adapter. Refer 
to the press tool manufacturer’s 
instructions for further details. 

4.  After the connection is complete, 

inspect the pressed joint to ensure 
the pipe has remained fully inserted 
during the pressing process.

5.  Pressure test the system to ensure 

a proper connection. If a leak is 
found, re-press the connection. 

 

Note: 

Uponor ProPEX copper 

press adapters are designed to 
leak air or water when improperly 

pressed to help installers identify 
improperly pressed connections. 

2½" and 3" adapter installation

1.  Assemble the joint by inserting the 

pipe into the adapter until it meets 
the pipe stop. Note that you can use 
clean water to ease the assembly 
process. Wetting the pipe and/or the 
adapter will ease the pipe-insertion 
process. Be sure to check the pipe 
insertion depth using the reference 
mark on the pipe’s outside diameter. 
(See step 5 in the previous Prepress 
section on 

page 5

.)  

 

Important!

 Only press the adapter 

when the pipe is fully inserted into 
the adapter.

2.  Select the appropriate size press 

ring. Open the press jaws and 
position them over the adapter. 
Align the groove in the press ring. 
Revolve the press ring around the 
adapter to the desired position.

3.  Attach the appropriate press 

adapter to the press tool and close 
the breach bolt. Attach the adapter 
ring to the press ring by depressing 
the jaw levers and inserting the 
claws as far as possible into the 
grooves of the press ring. Do 
not press the joint until the press 
adapter is correctly connected to 
the press ring.

4.  Press the tool’s trigger or actuation 

button and complete the pressing 
process. Refer to the press tool 
manufacturer’s instructions for 
further details. 

6  |  uponorpro.com

Содержание ProPEX

Страница 1: ...Uponor ProPEX copper press adapters installation guide ...

Страница 2: ...hts reserved Second edition September 2018 Second printing September 2018 Printed in the United States of America Uponor has used reasonable efforts in collecting preparing and providing quality information and material in this installation guide However system enhancements may result in modification of features or specifications without notice Uponor is not liable for installation practices that ...

Страница 3: ...verification the O ring is in place prior to pressing the joint Second the adapters are designed to leak when the connection is not pressed ensuring easy identification of un pressed joints at pressure test Quality assurance ProPEX copper press adapters are designed manufactured and listed to meet ASTM F1960 requirements for the ProPEX side and ASME B16 51 for the press side as well as conform to ...

Страница 4: ...al packaging until ready to install This ensures the adapters remain clean the O rings are protected from damage and onsite debris and the O ring lubricant does not dry out Be sure to keep unused adapters in their original packaging with any openings sealed to maintain cleanliness Minimum spacing requirements Install Uponor ProPEX copper press adapters with the following minimum spacing between ot...

Страница 5: ...pter to ensure the O ring is undamaged and seated correctly within the O ring groove The O ring should be free of cuts gouges or missing material at the surface If the O ring is damaged or missing do not use the adapter If the O ring is undamaged but is partially out of the groove gently move the O ring back into the groove If the O ring does not seat in the groove do not use the adapter 5 Insert ...

Страница 6: ...nd re press the connection Note Uponor ProPEX copper press adapters are designed to leak air or water when improperly pressed to help installers identify improperly pressed connections 2 and 3 adapter installation 1 Assemble the joint by inserting the pipe into the adapter until it meets the pipe stop Note that you can use clean water to ease the assembly process Wetting the pipe and or the adapte...

Страница 7: ...ion Jaw compatibility for 2 to 3 adapters Milwaukee M18 standard jaws RIDGID Viega standard jaws 2 49 16 2656 2 20453 3 49 16 2657 3 20548 Ring jaw 49 16 2659 Actuator 21878 Note The 2 to 3 press adapter connections feature a tag that breaks to indicate a completed connection This tag can be removed after completing the connection 5 After the connection is complete inspect the pressed joint to ens...

Страница 8: ...uponorpro com Uponor Ltd 6510 Kennedy Road Mississauga ON L5T 2X4 CANADA T 888 994 7726 F 800 638 9517 PrPXxCU_press_InsG_70158_0818 indd Copyright 2018 Uponor Printed in Canada ...