8.3 Setting log heat interface units
Date:
Setting log heat interface units
Site:
Type:
Serial no:
Component
Description
Setting
range
Factory
setting
Set
on
site
Set zone valve for
the flow rate
Setting value 1
2
3
4
5
6
7
8
9
1-9
continous
7
Kv value /
2 K P
deviation
0.05
0.09
0.14
0.20
0.26
0.32
0.49
0.57
0.67
TWB
The thermostatic hot water temperature limiter, infinitely adjustable downwards
35-70 °C
(limited to
60 °C)
6
Scale value 35-70 °C 1
2
3
4
5
6
7
8
Hot water
temperature
35 °C
40 °C
45 °C
50 °C
55 °C
60 °C
65 °C
70 °C
STW
Safety temperature monitor is fixed on a setting value
55 °C
Component
Description
Type
Cold water throttle
disc
Colour
Green
Black
Max. flow
l/min
15
19
Exchanger
Type
GBS-240H-24 (CU)
GVH-228H-24 (VacInox)
GBS-240H-40 (CU)
GVH-228H-40 (VacInox)
Heat meter distance
piece
Heat meter line Qn 1.5 installation length, 110 mm x ¾"
Other components/devices
Component
Description
Type
Not used
Installer, signature:
Installer, in capital letters:
Service partner:
24
|
Combi Port Base
|
Installation and operation manual
Содержание Combi Port PRO
Страница 1: ...Combi Port Base EN Installation and operation manual CD0000306 ...
Страница 33: ...Combi Port Base Installation and operation manual 33 ...
Страница 34: ...34 Combi Port Base Installation and operation manual ...
Страница 35: ...Combi Port Base Installation and operation manual 35 ...