36
4G CELLULAR
ALARM COMMUNICATOR
UL COMPLIANCE SECTION
INSTALLATION REQUIREMENTS
(cont.)
26. All connections to the UL battery must be made with stranded copper
insulated wires using the wire gauge and length recommendations in the
proceeding instruction. Additionally, connections to the battery shall be made
with insulated terminal connectors with a current rating of 2A or greater. All
batteries must be installed and replaced by qualified personnel. Furthermore,
the connections to the batteries are considered non-power limited circuits and
all non-power-limited high voltage wiring must be secured a minimum of 1/4”
inch away from all power-limited wiring.
27. The 4550-CB has two EOLR supervised inputs that report to the central
station when activated. These inputs are disabled in the default state and must
be enabled via the Dealer Web Site. Two insulated EOL resistors are enclosed
and only those insulated EOL resistors have been tested by UL. Additionally,
the resistor(s) must be fastened securely to the appropriate input, with no
means to open circuit, short to an adjacent circuit or cause a risk of electric
shock. See Figure 5 for further details.
FIGURE 5:
CONNECTIONS BETWEEN THE 4550-CB AND THE
EOL RESISTORS.