33
®
4550-CB
UL COMPLIANCE SECTION –
INSTALLATION REQUIREMENTS
(cont.)
5. The Model 4550-CB unit must be located within the same room as the alarm
panel and a maximum of 20 feet of the alarm panel. The 4550-CB must be
installed at the protected premises.
6. The wiring between the Model 4550-CB unit and the alarm panel must be in
conduit.
7. All power-limited wiring must be secured a minimum of 1/4 inch away from all
non-power-limited high voltage wiring, and all non-power-limited high voltage
wiring must be routed through a different conduit than any of the power-limited
wiring or cable. The only non-power limited wiring is between a battery and
the 4550-CB DC terminals.
8. Both the alarm panel’s DACT and the Model 4550-CB unit must be used for
alarm communications to the central monitoring station’s UL Listed digital
alarm receiver.
9. The telephone line connected to the RJ31X jack cannot be connected to a
PBX system.
10. The Model 4550-CB unit must be programmed to send a Test signal to the
central station a minimum of once every 24 hours.
11. The following troubles are to be programmed to output #1 or output #3 –
Loss of AC, low battery, telco loss, Cellular loss, and catastrophic failure
simultaneously. In addition, outputs 1 and 3 shall be connected to a reporting
zone on the alarm panel, and the zone must be set up as closed in the normal
state and open in the off-normal state. Activation of this zone must annunciate
locally at the keypad which shall be programmed to display the message “For
trouble see panel” or similar.
(UL COMPLIANCE SECTION continued next page)