810751-UTG-A-0313
Johnson Controls Unitary Products
5
— = Not applicable.
MA Modular Air Handlers use Coil Only Ratings.
RAC14J424S21(E)
MX20D
24.5
FC/MC60D
1470
41.0
31.6
16.25
13.25
MX20D
24.5
FC/MC62D
1470
41.5
32.2
16.25
13.50
MX20D
24.5
FC64D
1470
43.0
33.4
16.75
13.75
RAC14J484S21(E)
RFCX48DE
24.5
–
1600
46.0
32.6
15.25
12.50
RFCX60DE
24.5
–
1565
46.5
33.2
15.75
13.00
RFCX48DP
24.5
–
1610
45.5
32.0
14.25
11.75
RFCX60DP
24.5
–
1620
46.5
33.0
14.50
12.25
MX16C
21.0
FC/MC48C
1685
45.5
34.0
15.25
12.25
MX16C
21.0
FC60C
1420
45.5
31.0
15.75
13.00
MX20D
24.5
FC/MC48D
1525
45.5
33.4
15.50
12.75
MX20D
24.5
FC/MC60D
1470
45.5
31.2
16.00
13.00
MX20D
24.5
FC/MC62D
1605
47.0
34.0
16.00
13.25
MX20D
24.5
FC64D
1605
47.5
34.4
16.50
13.50
RAC14J604S21(E)
RFCX60DE
24.5
–
1835
56.5
39.6
14.50
12.50
RFCX60DP
24.5
–
1870
56.0
39.1
13.75
11.75
MX20D
24.5
FC/MC60D
1780
55.5
37.4
14.50
12.50
MX20D
24.5
FC/MC62D
1795
57.0
39.6
15.00
12.75
MX20D
24.5
FC64D
1795
57.5
41.0
15.25
13.00
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ANSI/AHRI Standard 210/240.
Cooling MBH based on 80°F entering air temperature, 50% RH (Relative Humidity), and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTUs at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTUs during a normal annual usage period for cooling divided by the total electric power input in
watt-hours during the same period.
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
COOLING CAPACITY - With Air Handler Coils (Continued)
UNIT
MODEL
AIR HANDLER
COIL
MODEL
1
COOLING
MODEL
WIDTH
RATED
CFM
NET MBH
SEER
EER
TOTAL
SENS.
14.5 SEER AC WITH AIR HANDLERS
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils (Coil Only Ratings)
UNIT MODEL
COIL
CFM RANGE
(MIN.-MAX.)
COOLING
MODEL
WIDTH
RATED
CFM
NET MBH
SEER
1
EER
TOTAL
SENS.
14.5 SEER AC COIL ONLY RATINGS
RAC14J184S21(E)
FC/MC/PC18
14.5,17.5
450-750
600
17.3
12.4
14.00
11.50
FC/MC/PC32
14.5
450-750
600
17.8
12.8
14.50
12.00
FC/MC/PC35
17.5,21.0
450-750
600
17.8
12.8
14.50
12.00
FC/MC/PC37
14.5
450-750
600
18.0
12.9
14.75
12.00
FC/MC/PC43
17.5,21.0
450-750
600
18.0
12.9
14.75
12.00
HD24
–
450-750
600
17.9
12.8
14.50
12.00
HD36
–
450-750
600
17.3
11.9
14.00
11.50
UC18
14.5,17.5
450-750
600
17.4
12.5
14.00
11.75
RAC14J244S21(E)
FC/MC/PC32
14.5
500-900
700
24.4
17.2
14.50
12.30
FC/MC/PC35
17.5,21.0
500-900
800
25.0
17.6
14.50
12.35
FC/MC/PC37
14.5
500-900
800
25.4
17.9
14.50
12.35
FC/MC/PC43
17.5,21.0
500-900
800
25.2
18.0
14.70
12.50
FC/MC/PC48
21.0,24.5
500-900
800
25.6
18.3
14.80
12.65
HD36
–
500-900
800
24.8
17.0
14.00
12.00
HD48
–
500-900
800
25.6
17.9
14.50
12.35
RAC14J304S21(E)
FC/MC/PC32
14.5
800-1200
1000
29.0
21.0
14.00
12.00
FC/MC/PC35
17.5,21.0
800-1200
1000
29.0
21.0
14.00
12.00
FC/MC/PC37
14.5
800-1200
1000
29.6
21.6
14.50
12.35
FC/MC/PC43
17.5,21.0
800-1200
1000
29.6
21.8
14.50
12.30
FC/MC/PC48
21.0,24.5
800-1200
1000
30.0
21.8
14.50
12.35
HD36
–
800-1200
1000
28.8
20.2
14.00
12.00
HD48
–
800-1200
1000
29.8
21.4
14.50
12.35
For notes see Page 6.