810751-UTG-A-0313
18
Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Continued on next page.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
RAC14J484S21(E)
INDOOR COIL MODEL NO.
FC/MC62
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1400
1600
1800
ID
DB
(°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID
WB
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C.
43.3
48.6
46.2
50.6
54.3
44.9
49.3
47.7
52.2
55.4
46.5
49.9
49.3
53.9
56.5
S.C.
43.2
39.3
33.6
33.2
26.2
44.8
42.1
35.6
35.0
27.1
46.4
45.0
37.6
36.7
27.9
KW
2.60
2.62
2.62
2.63
2.67
2.60
2.62
2.62
2.64
2.68
2.61
2.63
2.62
2.65
2.69
75
T.C.
41.8
46.2
44.3
48.6
52.4
43.2
47.0
45.7
50.2
53.6
44.7
47.7
47.2
51.7
54.7
S.C.
41.7
38.5
32.7
32.4
25.4
43.1
41.2
34.7
34.2
26.4
44.6
43.8
36.6
36.1
27.4
KW
3.00
3.02
3.02
3.03
3.06
3.01
3.02
3.02
3.04
3.07
3.01
3.03
3.02
3.04
3.08
85
T.C.
40.3
43.8
42.4
46.7
50.5
41.6
44.7
43.7
48.1
51.7
42.9
45.5
45.1
49.5
52.9
S.C.
40.2
37.8
31.9
31.6
24.7
41.5
40.2
33.7
33.5
25.8
42.8
42.6
35.6
35.4
26.9
KW
3.40
3.42
3.42
3.43
3.45
3.41
3.42
3.43
3.44
3.46
3.42
3.43
3.43
3.44
3.46
95
T.C.
38.8
41.4
40.5
44.7
48.6
40.0
42.4
41.7
46.0
49.9
41.1
43.3
42.9
47.3
51.1
S.C.
38.7
37.0
31.0
30.8
24.0
39.8
39.2
32.8
32.8
25.2
41.0
41.5
34.6
34.8
26.3
KW
3.80
3.82
3.83
3.84
3.84
3.81
3.82
3.83
3.83
3.84
3.82
3.82
3.83
3.83
3.85
105
T.C.
36.6
38.8
38.2
42.2
45.9
37.8
39.9
39.3
43.4
47.0
38.9
40.9
40.5
44.6
48.1
S.C.
36.6
35.8
29.8
29.8
22.9
37.7
37.7
31.7
31.9
24.1
38.8
39.6
33.6
33.9
25.3
KW
4.48
4.54
4.53
4.48
4.44
4.47
4.51
4.52
4.46
4.44
4.45
4.48
4.50
4.45
4.45
115
T.C.
34.6
36.3
36.0
39.7
43.2
35.7
37.4
37.0
40.8
44.2
36.8
38.5
38.0
41.9
45.2
S.C.
34.5
34.5
28.6
28.9
21.8
35.6
36.2
30.6
30.9
23.1
36.7
37.8
32.6
33.0
24.3
KW
5.14
5.23
5.22
5.10
5.03
5.10
5.17
5.19
5.08
5.03
5.06
5.11
5.16
5.06
5.03
125
T.C.
32.5
33.8
33.7
37.3
40.6
33.6
34.9
34.7
38.3
41.4
34.7
36.1
35.6
39.3
42.3
S.C.
32.4
33.3
27.4
27.9
20.8
33.5
34.7
29.5
30.0
22.1
34.6
36.0
31.6
32.2
23.3
KW
5.80
5.92
5.91
5.72
5.61
5.74
5.83
5.86
5.69
5.61
5.67
5.74
5.81
5.66
5.61
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC48
0.97
1.00
0.99
–
FC/MC/PC60
0.99
0.97
1.01
–
FC/MC62
1.00
1.00
1.00
–
FC64
1.01
1.03
0.99
–
HD60
1.01
0.99
1.01
–
UC48
0.97
1.00
0.99
–
UC60
0.98
0.97
1.00
RFCX48DE
–
1.00
0.99
0.96
RFCX60DE
–
1.01
1.01
0.93
RFCX48DP
–
0.99
0.98
1.01
RFCX60DP
–
1.01
1.01
0.99
MX16C
FC/MC48C
0.99
1.04
0.97
MX16C
FC60C
0.99
0.95
0.91
MX20D
FC/MC48D
0.99
1.02
0.93
MX20D
FC/MC60D
0.99
0.95
0.91
MX20D
FC/MC62D
1.02
1.04
0.93
MX20D
FC64D
1.03
1.05
0.92