Steel Body, Automatic Wood Pellet Feed Hot Water Boiler Operation and Maintenance 
Manual 

INFORMATION ON USE ERRORS 

 

PROBLEM 

CAUSE 

SOLUTION 

Insufficient heating 

 

Boiler heat transfer surfaces can be coated with 
soot and soot 

 

Fuel used may be of poor quality 
 

 

Pump may not start 
 

 

Inadequate space insulation 
 

 

The mode on the panel may be stuck. 

 

Clean the boiler surfaces. (the boiler should not burn) 

 

Change your fuel and take some quantity before 
refuelling and try to make it fit. 

 

Call for service, make sure the plug of the control 
panel is connected to the mains. 

 

Increase the thermal insulation of the place where the 
boiler is installed. 

 

Call service 

Burning is not satisfactory 

 

Low combustion air 
 

 

Chimney draft may be low 

 

Make sure that the fan is running, make sure that its 
flap is not closed. 

 

Check that there are no holes or cracks in any part of 
the chimney. If it is not enough, consult your chimney. 

 

Isolate the chimney. 

Smoke from the hopper 

 

The roving on the bunker may not touch or 
wear well on the surface 

 

Chimney draft may be low 

 

Make sure that the cover is fully pressed against the 
surface of the wick, if necessary renew it. 

 

Check that there are no holes or cracks in any part of 
the chimney. If it is not enough, consult your chimney. 
Have your chimney isolated. 

Excessive fuel consumption 

 

Poor quality fuel usage 

 

High flue traction 
 
 

 

Room insulation may be insufficient 

 

Change your fuel 

 

Check that there are no holes or cracks in any part of 
the chimney. If it is not enough, consult your chimney. 

 

Increase the thermal insulation of the place where the 
boiler is installed 

Smoke gas leakage from 
boiler covers 

 

Cover wicks may be worn 

 

Covers may be deformed 

 

Replace the wicks. 

 

Make sure that the combustion does not stand on the 
covers. For deformed covers, seek assistance from a 
specialist garage. 

Failure of the boiler to reach 
the set temperature 

 

The temperature sensor tip may have come out 
of its housing 

 

Replace the temperature sensor end of the control 
panel board by lifting the boiler top cover. Pour heat 
transfer oil into the housing. 

Partial heating of radiators 

 

Air in the radiator 

 

Remove air from the radiator air vents. 

 

Make sure that the automatic air vent plug is not 
tightened. 

Failure to ignite 

 

The amount of fuel in the first feed or the 
amount of dust with the fuel may be too high 

 

Ignition resistance may be defective 

 

The fan may not be running 

 

Eliminate pellet dust 

 

Reset and restart from the control panel 
 

 

Call service 

 

Call service 

Noisy sound from the boiler 

 

There may be air remaining in the boiler when 
the first water is filled 

 

Fill the boiler with water from the lowest position. 

If the boiler water 
temperature drops too high 
but the boiler still does not 
work 

 

Limit thermostat may be tripped 

 

After opening the front cover, turn the 
black plastic cover on the boiler and turn it 
over. Activate the limit thermostat by 
pressing the red pin. 

No power in control panel 

 

The power plug may not be plugged in. 

 

Electricity may be cut off 

 

The fuse in the control board may be blown. 

 

Plug in the power plug 

 

Try again when the electricity comes 

 

Replace the glass fuse on the control board in the 
control panel. 

 

 

 

ATTENTION 

In case of power failure, do not open the front cover and the bunker cover, do not add water 
to the boiler. 

 

ÜNLÜSOY YAPI MALZEMELERİ SANAYİ ve TİCARET LİMİTED ŞİRKETİ 

Address: Pancar Organize Sanayi Bölgesi, 2. Etap No:2,  Torbalı/İZMİR - TURKEY 

Tel: +90 444 35 32, Faks: +90232 469 2412 

www.unmak.com

 

Содержание Ecopel

Страница 1: ...el Compact Pellet Boiler Installation and User Manual NL SOY Yap Malzemeleri Sanayi ve Ticaret Ltd ti Pancar Organize Sanayi B lgesi 2 Etap No 2 Torbal ZM R Tel 444 35 32 Faks 0232 469 2412 www unmak...

Страница 2: ...RANSPORTATION 5 INSTALLATION LOCATION SELECTION 6 SAFETY WARNINGS 8 ELECTRICAL INSTALLATION INSTRUCTIONS 10 INFORMATION ON COMBUSTION 11 BOILER SPECIFICATIONS 13 RULES FOR HEATING INSTALLATION 15 CONT...

Страница 3: ...Operation and Maintenance Manual This booklet is covers below models ECOPEL 24 36 48 For Initial Start up Warranty Start up and Failure Notices please contact your local Authorized Service Centre or C...

Страница 4: ...for burning wood pellets only 6 8 10 mm diameter wood pellets are suitable for burning These boilers are only used for heating the heating system they are not suitable for direct domestic water heatin...

Страница 5: ...ATTENTION A hazardous situation may occur and failure to follow the precautions could result in minor personal injury or property damage WARNING Trapping of hands and feet should be avoided during tra...

Страница 6: ...he product must be of sufficient capacity In order to prevent damage to boiler outer plates and boiler during transportation help from the transport equipment such as forklift or pallet truck The cent...

Страница 7: ...hting is provided a system should be installed that does not dazzle but illuminates the apartment thoroughly The main switch and panels of the boiler room shall be placed around the entrance door and...

Страница 8: ...unker and to work comfortably A At least 80 cm to allow convenient use of the boiler cleaning arm and service intervention B The burner assembly is at least 100 cm C At least 80 cm in order to make fl...

Страница 9: ...ed from inside and outside and the cylindrical pipe is inserted into the rectangular chimney Fresh air must be provided to the area where the boiler is installed The dimensions specified in this manua...

Страница 10: ...nd therefore permanent damage Water should not be drained in the installation unless it is for maintenance or risk of freezing The system design should ensure that the ratio between the installation w...

Страница 11: ...rol cabinet must be connected to a wall panel with suitable grounding equipment All electrical connections must be made by authorized personnel in accordance with local regulations For each boiler roo...

Страница 12: ...nnected to an independent chimney which can provide minimum desired minimum draft It should be measured in 20 Pa with a manometer The part of the waste gas line between the boiler and the chimney shou...

Страница 13: ...bove the tiled roofs Chimney without chimney hood and chimney hood Incorrectly installed chimney and correctly installed chimney and chimney head DANGER Inadequate flue gas system can cause serious in...

Страница 14: ...Maximum Operating Temperature C Heating Line Flow Return inch 1 Filling Discharging Line inch Electricty V AC Hz Width W mm 960 960 1020 Depth D mm 700 700 700 Height H mm 1115 1230 1415 Height of Flo...

Страница 15: ...allowed to reach this group Manometer can be seen when the left front door of the boiler is opened Water pressure can be observed from the manometer while adding water When the left front door of the...

Страница 16: ...culation pump expansion tank safety valve is included with the boiler and you do not need to add to the installation separately The wiring diagram can be simply installed as shown For installations wi...

Страница 17: ...lower connection point Pressure reducer safety valve and expansion tank must be installed in the city water line entering the boiler Systems to be installed with Double Serpentine Hot Water Storage T...

Страница 18: ...e heating installation including installation pipes and radiators must be protected against corrosion Oxygen in the installation water causes rust and consequently material loss as a result of oxidati...

Страница 19: ...tion only when the installation is cold Considerations for central heating connected to old installations In a heating system that is used for a long time a protective layer black magnetite is formed...

Страница 20: ...hen the enter button is pressed in the menu it accepts the value written on the screen or enters into the menu displayed on the screen Escape Button Escape button is used to cancel without saving the...

Страница 21: ...rbox standby time 0 0 2000 sec P1 3 Fan speed 600 3000 rpm P1 4 Transition time 0 600 sec Power 2 P2 1 Gearbox feeding time 1 0 40 0 sec P2 2 Gearbox standby time 0 0 2000 sec P2 3 Fan speed 600 3000...

Страница 22: ...wn temperature 0 100 C V4 3 Pump run time at temperature rise 0 255 sec V4 4 Pump standby time at temperature rise 0 255 sec V4 7 Shut down time at power 0 sleep mode 0 20 min 0 cancel Various Setting...

Страница 23: ...empty there may not be an ignition at first After the error message appears on the screen reset it by pressing the ESC button for 5 seconds After the firing phases have passed the boiler goes to power...

Страница 24: ...it must be repaired and sealed Check the fan for proper operation An improperly balanced balanced fan makes periodic noises If there is fuel dust or ashes collected between the vanes of the fan it is...

Страница 25: ...he A1 bolts and remove the fan Then taking the A2 bolts gently remove the fan throat so that it does not hit the igniter You can remove the igniter by loosening the small setscrew bolt in the round ig...

Страница 26: ...r covers Cover wicks may be worn Covers may be deformed Replace the wicks Make sure that the combustion does not stand on the covers For deformed covers seek assistance from a specialist garage Failur...

Отзывы: