4
INSUTE202NP1215
SELECTION OF THE THERMOSTAT LOCATION
The thermostat must be mounted to a connection box on a wall facing the heating
unit, at around 1.5 m (5 feet) above the floor level, on a section of the wall exempt
from pipes or air ducts.
Do not install the thermostat in a location where temperature measurements
could be altered. For example:
• close to a window, on an external wall, or close to a door leading outside;
• exposed directly to the light or heat of the sun, a lamp, a fireplace or any other
heat source;
• close or in front of an air outlet;
• close to concealed ducts or a chimney; and
• in a location with poor air flow (e.g. behind a door), or with frequent air drafts
(e.g. head of stairs).
THERMOSTAT MOUNTING AND CONNECTION
1.
Cut off power supply on lead wires at the electrical panel in order to
avoid any risk of electric shock.
2. Ensure that the air vents of the thermostat are clean and clear of any
obstruction.
INSTALLATION