Turn on AC power and check the LED's for proper operation. The green LED lights to indicate
AC power. The red LED will flash every 40-60 seconds to indicate proper operation.

OPERATION, TESTING & MAINTENANCE

OPERATION:

 The smoke alarm is operating once the power is connected and turned on (the battery

must also be installed). When products of combustion are sensed, the unit sounds a loud alarm
which continues until the air is cleared.

This alarm incorporates the internationally recognized horn signal for evacuation. During alarm
mode, the horn produces three short beeps followed by a two second pause and then repeats.

STANDBY CONDITION:

 The red LED flashes once every 40-60 seconds to indicate the unit is

properly functioning.

LOCAL ALARM CONDITION:

 The red LED flashes rapidly and the unit emits a loud, pulsating

alarm sound.

REMOTE ALARM CONDITION:

 The red LED is off and the unit emits a loud, pulsating alarm.

GREEN LED:

 The green LED is on whenever AC power is turned on.

TESTING:

 Test by pushing the test button on the smoke alarm cover until the alarm sounds, then

release. The alarm sounds if all electronic circuitry, horn and battery are working. The alarm may
continue to sound for up to 10 seconds after the button is released. If no alarm sounds, the unit may
have a defective battery or other failure. 

Test the smoke alarm weekly to assure proper operation.

If you choose to use an aerosol smoke product to test the smoke alarm, be certain to use one
that has been Listed to Underwriters Laboratories, Inc. Safety Standards and use it only as
directed. Use of non-UL Listed products or improper use of UL Listed products may affect
the smoke alarm's sensitivity.

FALSE ALARMS "SILENCE" CONTROL: 

Units with the "silence" feature have the capability of

temporarily reducing the sensitivity of the alarm circuit for approximately 3-9 minutes. This feature is
to be used only when a known alarm condition such as smoke from cooking activates the smoke
alarm. The smoke alarm "silence" feature is activated by pushing the Hold to Silence button on the
smoke alarm cover for at least three seconds. The smoke alarm will automatically reduce sensitivity
and the red LED will light for approximately 3-9 minutes to indicate the alarm is in the temporary
silent condition. The smoke alarm will gradually regain normal sensitivity and sound the alarm if
particles of combustion are still present. The "silence" feature may be used repeatedly until the air
has cleared.

Page 5

NEVER use an open flame of any kind to test this unit. You might accidentally damage or set
fire to the unit or to your home. The built-in test switch accurately tests the unit's operation
as required by Underwriters Laboratories Inc. (UL).

(UTHA) Sensitivity Indicating Means

The sensitivity indicating means for this Smoke and Fire Alarm is the use of the analyzer for Smoke
Detectors Model 501-A or 501-A/Bat Aerosol Generator Manufactured by Gemini Scientific Corp.,
1122-B Aster Ave., Sunnyvale, CA 94086.

The Equivalent UL 268 Light obscuration %/Ft as measured by this instrument must be between
1.55% Obs./Ft. and 0.85% Obs./Ft (1.20 + 0.35% Obs./Ft.).

(UTHA) Go/No-Go Field Test

The Go/No-Go test for this Smoke and Fire Alarm is the use of a UL Listed can type aerosol smoke
detector tester. The instructions for the use of this tester are given on the container.

Содержание USI-5204

Страница 1: ...OR INSURANCE Homeowners and renters alike should continue to insure their lives and properties SMOKEALARMS CANNOTWORK WITHOUT POWER Battery operated units cannot work if the batteries are missing disconnected or dead if the wrong type of batteries are used or if the batteries are not installed correctly AC only powered units cannot work if the AC power is cut off for any reason If you are concerne...

Страница 2: ...102 mm vertically to the peak Sloped Ceilings Shed Ceilings Smoke alarms or smoke detectors mounted on a sloped ceiling having a rise greater than 1 ft in 8 ft 1 m in 8 m horizontally shall be located within 36 in 914 mm of the high side of the ceiling but not closer than 4 in 102 mm from the adjoining wall surface Tray Shaped Ceilings Smoke Alarms or smoke detectors shall be installed on the high...

Страница 3: ...h potting tests occur on the circuit or system Ref Section 550 17 National Electric Code 2002 Edition ELECTRICAL SHOCK HAZARD Turn off power to the area where you will install this unit at the circuit breaker or fuse box before beginning installation Failure to turn off the power before installation may result in serious electrical shock injury or death TAMPER LOCKING PIN To make your alarm somewh...

Страница 4: ...ally if a fire starts in a remote area of the dwelling This smoke alarm may be interconnected with as many as 11 other USI ELECTRIC model smoke alarms such as USI 1103 USI 1203 USI 1204 USI 1209 USI 1213 USI 2204 USI 3204 and 6 other units which may be a combination of Carbon Monoxide Alarms such as USI 7385 USI 7390 USI 7485 USI 7490 USI 7795 Heat Alarms USI 2430 or Relay Modules USI 960 for a to...

Страница 5: ...ed Use of non UL Listed products or improper use of UL Listed products may affect the smoke alarm s sensitivity FALSE ALARMS SILENCE CONTROL Units with the silence feature have the capability of temporarily reducing the sensitivity of the alarm circuit for approximately 3 9 minutes This feature is to be used only when a known alarm condition such as smoke from cooking activates the smoke alarm The...

Страница 6: ...ilobecquerel ofAmericium 241 a radioactive material The distribution of these ionization type smoke alarms is licensed by the U S Nuclear Regulatory Commission the consumer is exempt from any licensing or requirements If the smoke alarm is defective in any way do not tamper with the unit Return the unit for servicing See warranty for instructions or in warranty returns There will be a service char...

Страница 7: ... right to do so NATIONAL FIRE PROTECTION ASSOCIATION REQUIRED PROTECTION For your information the National Fire Protection Association s Standard 72 reads as follows 11 5 1 One and Two Family Dwelling Units 11 5 1 1 Smoke Detection Where required by applicable laws codes or standards for the specified occupancy approved single and multiple station smoke alarms shall be installed as follows 1 In al...

Страница 8: ...o cover the costs of return postage and handling You must include a proof of purchase receipt along with the returned product USI DOES NOT WARRANT AND SPECIFICALLY DISCLAIMS ANY WARRANTY WHETHER EXPRESS OR IMPLIED OF FITNESS FOR A PARTICULAR PURPOSE OTHER THAN THE WARRANTY CONTAINED HEREIN NO IMPLIED WARRANTY ON THIS PRODUCT CREATED BY STATE LAW SHALL EXTEND BEYOND THE TERM OF THIS WARRANTY UNLESS...

Отзывы: