2.

Wiring Instructions:

a.

The appropriate power supply is 120 Volt single phase power supplied from a non-switchable
circuit NOT protected by a ground fault circuit interrupter.

b.

Turn off main power to the circuit before wiring the smoke alarm.

c.

There are three pigtail leads (black, white and yellow) coming from the AC QUICK
CONNECTOR. The proper wire connection is as follows:

WIRES FROM QUICK CONNECTOR

CONNECT TO

BLACK

"HOT" side of AC line

WHITE

"NEUTRAL" side of AC line

YELLOW

Interconnect wires of other units

Early warning fire detection is best achieved by the installation of fire detection equipment in
all rooms and areas of the household as follows: A smoke alarm installed in each separate
sleeping area (in the vicinity of, but outside of, the bedrooms) and heat or smoke alarms in
living rooms, dining rooms, kitchens, hallways, attics, furnace rooms, closets, utility storage
rooms, basements and attached garages. Test the smoke alarm weekly to assure proper
operation.

3.

Attach the mounting plate to the electrical junction box.

4.

To activate 9 volt battery and alarm, hold the QUICK DRAW

(R)

 

battery drawer closed, pull and

remove the PULL-TAB.  Discard PULL-TAB.

5.

Plug the AC QUICK CONNECTOR into the alarm base. Push and turn the alarm clockwise
onto the mounting plate.

6.

See "TAMPER LOCKING PIN."

For units that are used as single smoke alarms, do not connect the yellow wire to anything. Insulate
this wire (tape it) in place to make certain the yellow wire cannot contact any metal parts.

Interconnected units can provide earlier warning of fire than stand-alone units, especially if
a fire starts in a remote area of the dwelling. This smoke alarm may be interconnected with
as many as 11 other USI ELECTRIC model smoke alarms such as USI-1103, USI-1203, USI-
1204, USI-1209, USI-1213, USI-2204, USI-3204 and 6 other units which may be a combination
of Carbon Monoxide Alarms such as USI-7385, USI-7390, USI-7485, USI-7490, USI-7795, Heat
Alarms/USI-2430 or Relay Modules/USI-960 for a total of not more than 18 interconnected
devices.

Interconnected CO alarms will only respond if a CO alarm / event initiates the alarm. All other
alarms remain silent.

Interconnected smoke alarms, heat alarms and relay modules will only respond if a smoke
alarm / event or heat alarm / event initiates the alarm. All CO alarms remain silent.

Note that units without battery backup will not respond during an AC power failure.

NOTE: Relay Modules/USI-960 will not respond if a CO alarm / event initiates the alarm.

Page 4

The yellow wire is used only for multiple station operation with USI ELECTRIC Model alarms
only. Connecting this yellow wire to any other circuits may result in damage. When alarms
are interconnected, all units must be powered from a single AC branch circuit. If local codes
do not permit be sure the neutral wire is common to both phases. The maximum wire run
distance between the first and last alarm/device in an interconnected system is 1,000 feet.
NOTE: Use standard household wire (18 gauge or larger, rated at least 300V, as required by
local codes) available at all electrical supply/hardware stores.

The wiring to be used shall be in accordance with the provisions of Articles 210 and 300.3(B)
of the National Electrical Code, ANSI/NFPA 70. In addition, the resistance of the interconnecting
wiring shall be a maximum of 10 Ohms.

INPUT:
120 VAC
60 HZ
.05A

Содержание USI-5204

Страница 1: ...OR INSURANCE Homeowners and renters alike should continue to insure their lives and properties SMOKEALARMS CANNOTWORK WITHOUT POWER Battery operated units cannot work if the batteries are missing disconnected or dead if the wrong type of batteries are used or if the batteries are not installed correctly AC only powered units cannot work if the AC power is cut off for any reason If you are concerne...

Страница 2: ...102 mm vertically to the peak Sloped Ceilings Shed Ceilings Smoke alarms or smoke detectors mounted on a sloped ceiling having a rise greater than 1 ft in 8 ft 1 m in 8 m horizontally shall be located within 36 in 914 mm of the high side of the ceiling but not closer than 4 in 102 mm from the adjoining wall surface Tray Shaped Ceilings Smoke Alarms or smoke detectors shall be installed on the high...

Страница 3: ...h potting tests occur on the circuit or system Ref Section 550 17 National Electric Code 2002 Edition ELECTRICAL SHOCK HAZARD Turn off power to the area where you will install this unit at the circuit breaker or fuse box before beginning installation Failure to turn off the power before installation may result in serious electrical shock injury or death TAMPER LOCKING PIN To make your alarm somewh...

Страница 4: ...ally if a fire starts in a remote area of the dwelling This smoke alarm may be interconnected with as many as 11 other USI ELECTRIC model smoke alarms such as USI 1103 USI 1203 USI 1204 USI 1209 USI 1213 USI 2204 USI 3204 and 6 other units which may be a combination of Carbon Monoxide Alarms such as USI 7385 USI 7390 USI 7485 USI 7490 USI 7795 Heat Alarms USI 2430 or Relay Modules USI 960 for a to...

Страница 5: ...ed Use of non UL Listed products or improper use of UL Listed products may affect the smoke alarm s sensitivity FALSE ALARMS SILENCE CONTROL Units with the silence feature have the capability of temporarily reducing the sensitivity of the alarm circuit for approximately 3 9 minutes This feature is to be used only when a known alarm condition such as smoke from cooking activates the smoke alarm The...

Страница 6: ...ilobecquerel ofAmericium 241 a radioactive material The distribution of these ionization type smoke alarms is licensed by the U S Nuclear Regulatory Commission the consumer is exempt from any licensing or requirements If the smoke alarm is defective in any way do not tamper with the unit Return the unit for servicing See warranty for instructions or in warranty returns There will be a service char...

Страница 7: ... right to do so NATIONAL FIRE PROTECTION ASSOCIATION REQUIRED PROTECTION For your information the National Fire Protection Association s Standard 72 reads as follows 11 5 1 One and Two Family Dwelling Units 11 5 1 1 Smoke Detection Where required by applicable laws codes or standards for the specified occupancy approved single and multiple station smoke alarms shall be installed as follows 1 In al...

Страница 8: ...o cover the costs of return postage and handling You must include a proof of purchase receipt along with the returned product USI DOES NOT WARRANT AND SPECIFICALLY DISCLAIMS ANY WARRANTY WHETHER EXPRESS OR IMPLIED OF FITNESS FOR A PARTICULAR PURPOSE OTHER THAN THE WARRANTY CONTAINED HEREIN NO IMPLIED WARRANTY ON THIS PRODUCT CREATED BY STATE LAW SHALL EXTEND BEYOND THE TERM OF THIS WARRANTY UNLESS...

Отзывы: